5-78
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state. In the case that the member is a structure containing more than one Dbpos, the Subscribed
to column identifies the particular Dbpos subscribed to.
RxGOOSE DSP1 DEFAULT STATE
Range: Intermediate-state, Off, On, Bad-state, Latest
Default: Latest
This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal and the DPS FlexLogic operands
when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and when the
RxGOOSE has lost its connection with the publisher. When this setting is selected to Latest, the value of @Master/
GGIO3.IndPos
ψψ
.stVal is Intermediate-state when the UR has just completed start-up and the selected RxGOOSE has
not yet received a message, and the latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
RxGOOSE analog inputs
Navigate to
Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Analog Inputs
.
There are
Add IED
and
Remove IED
buttons. The
Add IED
button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the
user select the ones to add.
Figure 5-31: RxGOOSE Analog Inputs panel
There are 32 RxGOOSE analog inputs.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...