5-108
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
For any change to take effect, restart the relay.
5.3.5.17 USB port
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
USB 2.0
This setting enables/disables the USB port on the graphical front panel. When the port function is "Enabled," a standard
USB serial cable allows a computer running the EnerVista UR Setup software to retrieve, display, and write settings either
individually or collectively, to display status and actual values, to initiate controls, and to retrieve and display event records,
oscillography records, data logger records, and disturbance records. Installation of the EnerVista software automatically
installs the drivers required to use this USB port.
DNP is not available using the USB port on the graphical front panel.
5.3.6 Modbus user map
SETTINGS
PRODUCT SETUP
MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the
ADDRESS
line (converted from hex to decimal format). The corresponding value (if programmed) displays in the
VALUE
line. A value of “0” in subsequent register
ADDRESS
lines automatically returns values for the previous
ADDRESS
lines
incremented by 1. An address value of “0” in the initial register means “none” and values of “0” display for all registers.
Different
ADDRESS
values can be entered as required in any of the register positions.
The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser;
enter the IP address of the L30 in a web browser and click the option.
5.3.7 Real-time clock
5.3.7.1 Menu
SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
USB 2.0
USB DEVICE PORT
FUNCTION: Enabled
Range: Disabled, Enabled
This setting applies to the USB port on the graphical front panel.
MODBUS USER MAP
ADDRESS 1: 0
VALUE: 0
Range: 0 to 65535 in steps of 1
ADDRESS 256:
0
VALUE: 0
Range: 0 to 65535 in steps of 1
REAL TIME
CLOCK
SYNCRONIZING SOURCE:
None
Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
Other, PP/PTP/IRIG-B/Other
REAL TIME CLOCK
EVENTS: Disabled
Range: Enabled, Disabled
IRIG-B SIGNAL TYPE:
None
Range: None, DC Shift, Amplitude Modulated
PRECISION TIME
PROTOCOL (1588)
See below
SNTP PROTOCOL
See below
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...