CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
7-13
7
•
Message
: "Unauthorized firmware attempt"
•
Latched target message
: No.
•
Description of problem
: A firmware upgrade operation was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the relay and try again.
•
Message
: "Unauthorized setting write"
•
Latched target message
: No.
•
Description of problem
: A setting write was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the settings and try again.
•
Message
: "An attempt to contact the Radius server has failed"
•
Latched target message
: No.
•
Description of problem
: The RADIUS authentication server is unavailable.
•
What to do
: Verify network connectivity and try again.
•
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
•
How often the test is performed: On relay power-up and afterwards once every 24 hours.
•
What to do: Contact the factory.
•
Description of problem
: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
•
What to do
: Update firmware to either of these builds.
•
7.2.2.4 HardFiber major self-test error messages
In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95
Plus
, see that product’s instruction manual.
•
Description of problem
: The number or type of installed hardware modules does not match the order code stored in
the CPU. The standard UR-series Equipment Mismatch self-test is extended to cover the possible presence of a
Process Card.
•
Severity
: Protection is not available and all contact outputs and shared outputs are de-asserted.
•
What to do
: Check all modules against the order code. Ensure they are inserted properly, and cycle the control power.
If a module has intentionally been added or removed use the Update Order Code command to notify the relay that the
current module configuration is correct.
FIRMWARE LOCK
SETTING LOCK
SERVER UNAVAILABLE
DOS PARTITION ALARM:
SELF-TEST ERROR
PROTOTYPE FIRMWARE:
Self Test Error
EQUIPMENT MISMATCH
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...