5-184
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
5.5.8.20 Control blocks
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
90–5 R-SV CB 1 CONFIGURATION
R-SV CB1 SVENA
— The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where “1”= Enabled and “0”=Disabled. The figure shows the logic for setting the SvEna control bit.
Figure 5-94: Logic for setting SvEna control bit
R-SV CB1 CLIENT CONTRL
— This setting determines if a client can write to the reserve bit. When the assigned FlexLogic
operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. When the FlexLogic operand
is a logic 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative response with
the appropriate Service Error is returned to the client.
90-5 R-SV CB 1
CONFIGURATION
R-SV CB1 SVENA:
Off
Range: FlexLogic operand
R-SV CB1 CLIENT CTRL:
Off
Range: FlexLogic operand
R-SV CB1 SVENA DFLT:
Off
Range: FlexLogic operand
R-SV CB1 CONFREV:
1
Range: 1 to 4294967295
R-SV CB1 PRIORITY:
4
Range: 0 to 7
R-SV CB1 CSCP CLASS:
Expedited Forwarding
Range: None, Expedited Forwarding
R-SV CB1 VLAN ID:
0
Range: 0 to 4095
R-SV CB1 APPID:
0
Range: 0 to 16383
R-SV CB1 DEST IP:
224.0.0.0
Range: 0 to 255.255.255.255
R-SV CB1 SECURITY:
0
Range: 0 to 2
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...