5-32
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Rolling Mode Page 1 to 10
Range: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Phasors 1…6, Tabular 1…5, Event Records, Targets
Default: Product Information
These settings specify the pages to display on the graphical front panel while in rolling mode.
The "Annunciator" selection without a page number specifies the first annunciator page in the following sequence:
–
The first annunciator page that contains an annunciator window that is in alarm (fast flash)
–
The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the
RESET
button.
–
The first annunciator page that contains an annunciator window that is in abnormal state
–
Annunciator page 1
Whenever an annunciator window changes state the list is re-evaluated, which can result in the display of a different
annunciator page in the rolling sequence.
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages.
5.3.3.3 Metering editor
This feature creates tables of actual/metered values for the graphical front panel. It configures the content that displays in
the Metering Tab pushbutton. An actual value, status, or text can be displayed. Five tabular metering pages can be
configured. There also can be a phasor page for each configured AC source, and these pages are not configurable.
The path is
Settings > Product Setup > Graphical Panel > Metering Editor
.
Set the Current Page, Page Name, Layout, configure the top inputs, then the cells. The 16 inputs at the top of the page are
used as inputs for the
Status Index
fields. Click the
Preview
button to view the page.
For a phasor diagram, configure the source under
Settings > System Setup > Signal Sources
. The diagram is then
viewable by pushing the
Metering
Tab pushbutton on the graphical front panel. The Metering Editor is not used.
The figures show setup and preview for monitoring actual values in a table on the graphical front panel.
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...