5-196
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-25: FlexLogic gate characteristics
SELF-DIAGNOSTICS
(See Relay Self-tests
descriptions in
Chapter 7:
Commands and
Targets
)
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
IRIG-B FAILURE
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
RxGOOSE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
SETTING CHANGED
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is weak or not functioning. Replace as outlined in the
Maintenance chapter.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
"Bad IRIG-B Signal" self-test. See Chapter 7: Commands and Targets.
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in Chapter 7: Commands and Targets.
See description in Chapter 7: Commands and Targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE messages are not being received
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
SNTP server is not responding
See description in Chapter 7: Commands and Targets
Monitors ambient temperature and maximum operating temperature
The product
SETUP > INSTALLATION > RELAYS SETTINGS
setting is not
programmed
Any device settings changed over any available interface; operand is
asserted for at least one second and then self-reset
TEMPERATURE
MONITOR
TEMP MONITOR
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
USER-
PROGRAMMABLE
PUSHBUTTONS
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
Pushbutton number 1 is in the “On” position
Pushbutton number 1 is in the “Off” position
Any of 12 pushbuttons is in the “On” position
PUSHBUTTON 2 to 6, 12, or 16
depending on front panel
Same set of operands as PUSHBUTTON 1
Gates
Number of inputs
Output is ‘1’ (= ON) if...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
Operand type
Operand syntax
Operand description
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...