CHAPTER 5: SETTINGS
TRANSDUCER INPUTS/OUTPUTS
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-313
5
Figure 5-167: Direct inputs/outputs logic (example for L90 shown)
5.10 Transducer inputs/outputs
5.10.1 DCmA inputs
SETTINGS
TRANSDUCER I/O
DCMA INPUTS
DCMA INPUT H1(U8)
Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
Before the DCmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
DCmA input channels are arranged in a manner similar to CT and VT channels. Configure the individual channels with the
settings shown here.
DCMA INPUT H1
DCMA INPUT H1
FUNCTION: Disabled
Range: Disabled, Enabled
DCMA INPUT H1 ID:
DCMA Ip 1
Range: up to 20 alphanumeric characters
DCMA INPUT H1
UNITS:
μ
A
Range: six alphanumeric characters
DCMA INPUT H1
RANGE: 0 to -1 mA
Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5
mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m
DCMA INPUT H1 MIN
VALUE: 0.000
Range: –9999.999 to +9999.999 in steps of 0.001
DCMA INPUT H1 MAX
VALUE: 0.000
Range: –9999.999 to +9999.999 in steps of 0.001
The L30 is provided with optional DCmA capability. This feature is specified as an option at the time of ordering.
See the Order Codes section in chapter 2 for details.
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...