CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-129
5
PUSHBTN 1 LOCAL
— This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME
— This setting applies only to “Self-Reset” mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by
PUSHBTN 1 SET
remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL
— This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the
PUSHBUTTON 1 ON
operand. This setting is not applied to
pushbuttons 9 to 16 on the graphical front panel, where the label background shows the orange glow color for the "on"
state.
PUSHBTN 1 MESSAGE
— This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 OFF TEXT
settings. This settings has no effect on the
graphical front panel.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays when
the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the
FLASH MESSAGE TIME
setting.
When set to "High Priority", the duration of the off message is as specified by the
FLASH MESSAGE TIME
setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS
— If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
The figures show the user-programmable pushbutton logic.
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...