L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
9-1
L30 Line Current Differential System
Chapter 9: Commissioning
Commissioning
9.1 Testing
9.1.1 Channel testing
The communications system transmits and receives data between two or three terminals for the 87L function. The system
is designed to work with multiple channel options, including direct and multiplexed optical fiber, G.703, and RS422. The
speed is 64 Kbaud in a transparent synchronous mode with automatic synchronous character detection and CRC
insertion.
The Local Loopback Channel Test verifies the L30 communication modules are working properly. The Remote Loopback
Channel Test verifies the communication link between the relays meets requirements (BER less than 10–4). All tests are
verified by using the internal channel monitoring and the monitoring in the Channel Tests. All of the tests presented in this
section must be either OK or PASSED.
1.
Verify that a type “W” module is placed in slot ‘W’ in both relays (for example W7J).
2.
Interconnect the two relays using the proper media (for example, single-mode fiber cable) observing correct
connection of receiving (Rx) and transmitting (Tx) communications paths and turn power on to both relays.
3.
Verify that the Order Code in both relays is correct.
4.
Cycle power off/on in both relays.
5.
Verify and record that both relays indicate In Service on the front display.
6.
Make the following setting change in both relays:
GROUPED ELEMENTS
GROUP 1
CURRENT DIFFERENTIAL
ELEMENTS
CURRENT DIFFERENTIAL
CURRENT DIFF FUNCTION
: “Enabled.”
7.
Verify and record that both relays have established communications with the following status checks:
ACTUAL VALUES
STATUS
CHANNEL TESTS
CHANNEL 1 STATUS
: “OK”
ACTUAL VALUES
STATUS
CHANNEL TESTS
CHANNEL 2 STATUS
: “OK” (If used)
8.
Make the following setting change in both relays:
TESTING
TEST MODE
: “Enabled.”
9.
Make the following setting change in both relays:
TESTING
CHANNEL TESTS
LOCAL LOOPBACK TEST
LOCAL LOOPBACK CHANNEL NUMBER
: "1"
10. Initiate the Local Loopback Channel Tests by making the following setting change:
TESTING
CHANNEL TESTS
LOCAL LOOPBACK TEST
LOCAL LOOPBACK FUNCTION
: "Yes"
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...