CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-223
5
The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication
Instantaneous Overcurrent (IOC) Element Response to Saturated Waveforms in UR Series Relays (
).
FUNCTION
— This setting enables and disables the phase instantaneous overcurrent protection element.
SOURCE
— Selects the signal source for the phase instantaneous overcurrent protection element.
PICKUP
— Specifies the phase instantaneous overcurrent pickup level in per-unit values.
DELAY
—Delays the assertion of the
PHASE IOC OP
operands. It is used to achieve timing coordination with other elements
and relays.
RESET DELAY
— Specifies a delay for the reset of the phase instantaneous overcurrent element between the operate output
state and the return to logic 0 after the input passes outside the defined pickup range. This setting is used to ensure that
the relay output contacts are closed long enough to ensure reception by downstream equipment.
BLOCK A
— Assertion of the operand assigned to this setting block’s phase A of the phase instantaneous overcurrent
element.
EVENTS
— Enables and disables the logging of phase instantaneous overcurrent events in the sequence of events recorder.
Figure 5-111: Phase instantaneous overcurrent 1 logic
5.7.4.5 Phase directional overcurrent (ANSI 67P, IEC PDOC/PTOC)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE DIRECTIONAL 1(2)
PHASE
DIRECTIONAL 1
PHASE DIR 1
FUNCTION: Disabled
Range: Disabled, Enabled
PHASE DIR 1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2
PHASE DIR 1 BLOCK:
Off
Range: FlexLogic operand
PHASE DIR 1
ECA: 30°
Range: 0 to 359° in steps of 1
PHASE DIR POL V1
THRESHOLD: 0.700 pu
Range: 0.004 to 3.000 pu in steps of 0.001
PHASE DIR 1 BLOCK
WHEN V MEM EXP: No
Range: No, Yes
PHASE DIR 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...