CHAPTER 5: SETTINGS
SYSTEM SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-183
5
Table 5-20: FlexLogic operands supported by aggregator
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1 NAME
— A user-defined visible string of characters (maximum 56) to identify the source of the stream.
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT
— This setting determines the physical ports through which the synchrophasor traffic is
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
— This setting selects the UDP port number that is used by this dataset for network reporting.
A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR 1: NUMBER OF ASDUs
— This setting sets the number of Application Service Data Units (ASDUs) from 1
through to 4.
Table 5-21: Number of ASDUs
Operand type
Operand syntax
Operand description
ELEMENT:
Synchrophasor, phasor data,
concentrator
AGTR1 PDC CNTRL 1
Phasor data concentrator asserts control bit 1, as
received via the network
as above
AGTR1 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR1 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network
as above
AGTR2 PDC CNTRL 1
Phasor data concentrator asserts control bit 1 as
received via the network
as above
AGTR2 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR2 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
NAME:
Range: 56-character ASCII text (blank by default)
PMU AGGREGATOR 1
PORT: 1
Range: 1, 2, 3
PMU AGGREGATOR 1
UDP PORT: 102
Range: 0 to 65534 in steps of 1
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
Range: 1 to 4
Settings for
ASDU
Transmission
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...