CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-89
5
Figure 5-38: Deadband settings with .db suffix
GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Figure 5-39: Deadband settings
Deadband settings are entered in UR Setup software in units of percent of the difference between the "max." and "min." of
the associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings
is 0.000 to 100.000% in steps of 0.001. The default value is 0.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
•
Phase current — 46 x phase CT primary setting
•
Neutral current — 46 x ground CT primary setting
•
Ground current (sensitive ground CT) — 4.6 x sensitive ground CT primary setting
•
Phase, phase-to-phase, and sequence voltage — 275 x phase VT ratio setting
•
Auxiliary voltage — 275 x auxiliary VT ration setting
•
Power (real, reactive, apparent, 3-phase, and 1-phase) — 4 × phase CT primary setting × 1.5 × VT Secondary setting ×
VT ratio setting
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...