CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-73
5
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s
TxGOOSE ETYPE APPID
setting.
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
Default: empty string
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if the logical device containing the publishing control block has "ldName"
configured, otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing
control block.
The L30 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName
setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the
publisher is a UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for
example "GoCB01". If the publisher is a UR 7.40 series device, <GoCBName> is as specified earlier in the TxGOOSE
section of this chapter.
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default: empty string
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's
TxGOOSE datSet
setting. If the publisher is a UR 7.40
series device, datSet is as specified in the DataSets section of this chapter.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's
TxGOOSE ConfRev
setting.
R-RxGOOSE1 RECEPTION MODE
Range: SSM, ASM, Unicast
Default: SSM
When the
RxGOOSE1 MODE
setting is other than R-GOOSE the value of this setting is not used. Otherwise it selects the
R-GOOSE reception mode.
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...