CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
7-9
7
•
Latched target message
: Yes.
•
Description of problem
: Module hardware failure detected.
•
How often the test is performed
: Module dependent.
•
What to do
: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
•
Latched target message
: Yes.
•
Description of problem
: Internal process disruption detected.
•
How often the test is performed
: Module dependent.
•
What to do
: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
•
Latched target message
: Yes.
•
Description of problem
: The battery is weak or not functioning. It powers the real time clock. This message displays as
Battery Fail in the event records. When the battery weakness reaches a critical level, the message displays persistently
on the front panel and no front panel key navigation is possible.
•
How often the test is performed
: The battery is monitored every five seconds. The error message displays after 60
seconds if the problem persists
.
•
What to do
: Replace the battery as outlined in the Maintenance chapter.
•
Latched target message
: No.
•
Description of problem
: Direct input and output settings are configured for a ring, but the connection is not in a ring.
•
How often the test is performed
: Every second
.
•
What to do
: Check direct input and output configuration and wiring.
•
Latched target message
: No.
•
Description of problem
: A bad IRIG-B input signal has been detected.
•
How often the test is performed
: Monitored whenever an IRIG-B signal is received.
•
What to do
: Ensure the following:
–
The IRIG-B cable is properly connected.
–
Proper cable functionality (that is, check for physical damage or perform a continuity test).
–
The IRIG-B receiver is functioning.
–
Check the input signal level (it can be less than specification).
If none of these apply, then contact the factory.
DIAGNOSTIC ALARM:
with 2nd line detail
MAINTENANCE ALERT:
Replace Battery
MAINTENANCE ALERT:
Direct I/O Ring Break
MAINTENANCE ALERT:
Bad IRIG-B Signal
Содержание L30
Страница 10: ...x L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 126: ...3 68 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 214: ...4 88 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 582: ...7 16 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 598: ...9 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 622: ...10 24 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 670: ...A 18 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 678: ...C 6 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 682: ...D 4 L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 686: ...iv L30 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...