B-76
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F101
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled, 1 = Enabled
F103
ENUMERATION: CURVE SHAPES
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B,
3 = FlexCurve C
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
Bitmask
Curve shape
Bitmask
Curve shape
0
IEEE Mod Inv
9
IAC Inverse
1
IEEE Very Inv
10
IAC Short Inv
2
IEEE Ext Inv
11
I2t
3
IEC Curve A
12
Definite Time
4
IEC Curve B
13
FlexCurve A
5
IEC Curve C
14
FlexCurve B
6
IEC Short Inv
15
FlexCurve C
7
IAC Ext Inv
16
FlexCurve D
8
IAC Very Inv
Bitmask
Value
Bitmask
Value
Bitmask
Value
0
300
4
9600
8
115200
1
1200
5
19200
9
14400
2
2400
6
38400
10
28800
3
4800
7
57600
11
33600
Bitmask
Element
0
Phase Instantaneous Overcurrent 1
1
Phase Instantaneous Overcurrent 2
2
Phase Instantaneous Overcurrent 3
3
Phase Instantaneous Overcurrent 4
4
Phase Instantaneous Overcurrent 5
5
Phase Instantaneous Overcurrent 6
6
Phase Instantaneous Overcurrent 7
7
Phase Instantaneous Overcurrent 8
16
Phase Time Overcurrent 1
17
Phase Time Overcurrent 2
18
Phase Time Overcurrent 3
19
Phase Time Overcurrent 4
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...