5-224
C60 Breaker Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
and will start the transfer timer. Since the fault is permanent the protection will trip again initiating the autoreclose
scheme that will be sent to Lockout by the
SHOT COUNT = MAX
signal.
•
Transient Fault
: When the first reclose output signal is sent to close Breaker 1, the reset timer is started. The close
Breaker 1 signal initiates the transfer timer that times out and sends the close signal to the second breaker. If the reclo-
sure sequence is successful (both breakers closed and there is no initiating signal) the reset timer will time out, return-
ing the scheme to the reset state with the shot counter set to 0. The scheme will be ready for a new reclose cycle.
AR BKR1(2) RECLS FAIL:
If the selected sequence is “1–2” or “2–1” and after the first or second reclose attempt the breaker fails to close, there are
two options. If the
AR BKR 1(2) FAIL OPTION
is set to “Lockout”, the scheme will go to lockout state. If the
AR BKR 1(2) FAIL
OPTION
is set to “Continue”, the reclose process will continue with Breaker 2. At the same time the shot counter will be
decreased (since the closing process was not completed).
SCHEME RESET AFTER RECLOSURE:
When a reclose output signal is sent to close either breaker 1 or 2 the reset timer is started. If the reclosure sequence is
successful (there is no initiating signal and the breakers are closed) the reset timer will time out, returning the scheme to
the reset state, with the shot counter set to 0, making it ready for a new reclose cycle.
In two breaker schemes, if one breaker is in the out-of-service state and the other is closed at the end of the reset time, the
scheme will also reset. If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open
the scheme will be sent to Lockout.
The reset timer is stopped if the reclosure sequence is not successful: an initiating signal present or the scheme is in Lock-
out state. The reset timer is also stopped if the breaker is manually closed or the scheme is otherwise reset from lockout.
LOCKOUT:
When a reclose sequence is started by an initiate signal the scheme moves into the reclose-in-progress state and starts the
incomplete sequence timer. The setting of this timer determines the maximum time interval allowed for a single reclose
shot. If a close breaker 1 or 2 signal is not present before this time expires, the scheme goes to “Lockout”.
There are four other conditions that can take the scheme to the Lockout state, as shown below:
•
Receipt of ‘Block’ input while in the reclose-in-progress state
•
The reclosing program logic: when a 3P Initiate is present and the autoreclose mode is either 1 Pole or 3Pole-A (3 pole
autoreclose for single pole faults only)
•
Initiation of the scheme when the count is at the maximum allowed
•
If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open the scheme will be
sent to Lockout. The scheme will be also sent to Lockout if one breaker fails to reclose and the setting
AR BKR FAIL
OPTION
is set to “Lockout”.
Once the Lockout state is set it will be latched until one or more of the following occurs:
•
The scheme is intentionally reset from Lockout, employing the Reset setting of the Autorecloser;
•
The Breaker(s) is(are) manually closed from panel switch, SCADA or other remote control through the
AR BRK MAN
CLOSE
setting;
•
10 seconds after breaker control detects that breaker(s) were closed.
BREAKER OPEN BEFORE FAULT:
A logic circuit is provided that inhibits the close breaker 1 and close breaker 2 outputs if a reclose initiate (RIP) indicator is
not present within 30 ms of the Breaker Any Phase Open input. This feature is intended to prevent reclosing if one of the
breakers was open in advance of a reclose initiate input to the recloser. This logic circuit resets when the breaker is closed.
TRANSFER RECLOSE WHEN BREAKER IS BLOCKED:
1.
When the reclosing sequence 1-2 is selected and Breaker 1 is blocked (
AR BKR1 BLK
operand is set) the reclose signal
can be transferred direct to the Breaker 2 if
AR TRANSFER 1 TO 2
is set to “Yes”. If set to “No”, the scheme will be sent to
Lockout by the incomplete sequence timer.
2.
When the reclosing sequence 2-1 is selected and Breaker 2 is blocked (
AR BKR2 BLK
operand is set) the reclose signal
can be transferred direct to the Breaker 1 if
AR TRANSFER 2 TO 1
is set to “Yes”. If set to “No” the scheme will be sent to
Lockout by the incomplete sequence timer.
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...