B-48
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
8DC8
...Repeated for Digital Element 45
8DDE
...Repeated for Digital Element 46
8DF4
...Repeated for Digital Element 47
8E0A
...Repeated for Digital Element 48
Trip Bus (Read/Write Setting) (6 modules)
8ED0
Trip Bus 1 Function
0 to 1
---
1
F102
0 (Disabled)
8ED1
Trip Bus 1 Block
0 to 4294967295
---
1
F300
0
8ED3
Trip Bus 1 Pickup Delay
0 to 600
s
0.01
F001
0
8ED4
Trip Bus 1 Reset Delay
0 to 600
s
0.01
F001
0
8ED5
Trip Bus 1 Input (16 items)
0 to 4294967295
---
1
F300
0
8EF5
Trip Bus 1 Latching
0 to 1
---
1
F102
0 (Disabled)
8EF6
Trip Bus 1 Reset
0 to 4294967295
---
1
F300
0
8EF8
Trip Bus 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8EF9
Trip Bus 1 Events
0 to 1
---
1
F102
0 (Disabled)
8EFA
Reserved (8 items)
0 to 1
---
1
F001
0
8F02
...Repeated for Trip Bus 2
8F34
...Repeated for Trip Bus 3
8F66
...Repeated for Trip Bus 4
8F98
...Repeated for Trip Bus 5
8FCA
...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (8 modules)
9000
FlexElement 1 Function
0 to 1
---
1
F102
0 (Disabled)
9001
FlexElement 1 Name
---
---
---
F206
“FxE 1”
9004
FlexElement 1 InputP
0 to 65535
---
1
F600
0
9005
FlexElement 1 InputM
0 to 65535
---
1
F600
0
9006
FlexElement 1 Compare
0 to 1
---
1
F516
0 (LEVEL)
9007
FlexElement 1 Input
0 to 1
---
1
F515
0 (SIGNED)
9008
FlexElement 1 Direction
0 to 1
---
1
F517
0 (OVER)
9009
FlexElement 1 Hysteresis
0.1 to 50
%
0.1
F001
30
900A
FlexElement 1 Pickup
-90 to 90
pu
0.001
F004
1000
900C
FlexElement 1 DeltaT Units
0 to 2
---
1
F518
0 (Milliseconds)
900D
FlexElement 1 DeltaT
20 to 86400
---
1
F003
20
900F
FlexElement 1 Pickup Delay
0 to 65.535
s
0.001
F001
0
9010
FlexElement 1 Reset Delay
0 to 65.535
s
0.001
F001
0
9011
FlexElement 1 Block
0 to 4294967295
---
1
F300
0
9013
FlexElement 1 Target
0 to 2
---
1
F109
0 (Self-reset)
9014
FlexElement 1 Events
0 to 1
---
1
F102
0 (Disabled)
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
Fault Report Settings (Read/Write Setting)
9200
Fault Report 1 Source
0 to 5
---
1
F167
0 (SRC 1)
9201
Fault Report 1 Trigger
0 to 4294967295
---
1
F300
0
9203
Fault Report 1 Z1 Magnitude
0.01 to 250
ohms
0.01
F001
300
9204
Fault Report 1 Z1 Angle
25 to 90
degrees
1
F001
75
9205
Fault Report 1 Z0 Magnitude
0.01 to 650
ohms
0.01
F001
900
9206
Fault Report 1 Z0 Angle
25 to 90
degrees
1
F001
75
9207
Fault Report 1 Line Length Units
0 to 1
---
1
F147
0 (km)
9208
Fault Report 1 Line Length
0 to 2000
---
0.1
F001
1000
9209
Fault Report 1 VT Substitution
0 to 2
---
1
F270
0 (None)
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...