6-12
C60 Breaker Protection System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
MMS TCP
— The number of IEC 61850 connections remaining.
PMU TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number
of aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with
a PMU. The remaining number of aggregators displays here.
6.2.21 PARALLEL REDUNDANCY PROTOCOL (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
PATH: ACTUAL VALUES
STATUS
PRP
The C60 Breaker Protection System is provided with optional PRP capability. This feature is specified as a
software option at the time of ordering. See the
Order Codes
section in chapter 2 for details.
TOTAL RECEIVED PORT A
is a counter for total messages received (either from DANPs or from SANs) on Port A.
TOTAL RECEIVED PORT B
is a counter for total messages received (either from DANPs or from SANs) on Port B.
TOTAL ERRORS
is a counter for total messages received with an error (bad port code, frame length too short).
MISMATCHES PORT A
is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
MISMATCHES PORT B
is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
PRP
Total Rx Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Rx Port B:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Total Errors:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port A:
Range: 0 to 4G, blank if PRP disabled
MESSAGE
Mismatches Port B:
Range: 0 to 4G, blank if PRP disabled
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...