5-12
C60 Breaker Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the
Settings > Product
Setup > Security
menu item to display the security settings window.
The
Remote Settings Authorized
setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If
this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required. If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The
Access Authorized Timeout
setting represents the timeout delay remote setting access. This setting is applicable
when the
Remote Settings Authorized
setting is programmed to any operand except “On” or “Off”. The state of the Flex-
Logic operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted
and the timer programmed with the
Access Authorized Timeout
setting value is started. When this timer expires, remote
setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected,
the timeout is restarted. The status of this timer is updated every 5 seconds.
c) ENERVISTA SECURITY
ENABLING THE SECURITY MANAGEMENT SYSTEM
The EnerVista security system allows an administrator to manage access privileges of multiple users to the EnerVista appli-
cation.
It is disabled by default to allow the administrator direct access to the EnerVista software immediately after installation.
When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before
placing the device in service.
To enable the security system and require password use:
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...