5.8 INPUTS AND OUTPUTS
5 SETTINGS
5
Example 1: Extending input/output capabilities of a C60 relay
Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable
logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED,
such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are con-
nected via single-channel digital communication cards as shown below.
Figure 5–119: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
The
Cont Ip 1 On
operand of UR IED 2 is now available in UR IED 1 as
DIRECT INPUT 5 ON
.
Example 2: Interlocking busbar protection
A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.
Figure 5–120: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME
Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
would trip the bus upon detecting a fault and applying a short coordination time delay.
The following settings should be applied (assume Bit 3 is used by all 3 devices to send the blocking signal and Direct Inputs
7, 8, and 9 are used by the receiving device to monitor the three blocking signals):
UR IED 2:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 3:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 4:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 1:
DIRECT INPUT 7 DEVICE ID
: "2"
DIRECT INPUT 7 BIT NUMBER
: "3"
DIRECT INPUT 7 DEFAULT STATE
: select "On" for security, select "Off" for dependability
DIRECT INPUT 8 DEVICE ID
: "3"
DIRECT INPUT 8 BIT NUMBER
: "3"
DIRECT INPUT 8 DEFAULT STATE
: select "On" for security, select "Off" for dependability
UR IED 1:
DIRECT INPUT 5 DEVICE ID
= “2”
DIRECT INPUT 5 BIT NUMBER
= “12”
UR IED 2:
DIRECT OUT 12 OPERAND
= “Cont Ip 1 On”
UR IED 1
TX1
RX1
UR IED 2
TX1
RX1
842712A1.CDR
UR IED 1
UR IED 2
UR IED 4
UR IED 3
BLOCK
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...