B.4 MEMORY MAPPING
B
5A0B
Phase Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5A0C
Phase Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5A0D
Reserved (6 items)
0 to 1
---
1
F001
0
5A13
...Repeated for Phase Instantaneous Overcurrent 2
5A26
...Repeated for Phase Instantaneous Overcurrent 3
5A39
...Repeated for Phase Instantaneous Overcurrent 4
5A4C
...Repeated for Phase Instantaneous Overcurrent 5
5A5F
...Repeated for Phase Instantaneous Overcurrent 6
5A72
...Repeated for Phase Instantaneous Overcurrent 7
5A85
...Repeated for Phase Instantaneous Overcurrent 8
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5B01
Neutral Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5B02
Neutral Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5B03
Neutral Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5B04
Neutral Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5B05
Neutral Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5B06
Neutral Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5B07
Neutral Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5B09
Neutral Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5B0A
Neutral Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5B0B
Reserved (6 items)
0 to 1
---
1
F001
0
5B11
...Repeated for Neutral Time Overcurrent 2
5B22
...Repeated for Neutral Time Overcurrent 3
5B33
...Repeated for Neutral Time Overcurrent 4
5B44
...Repeated for Neutral Time Overcurrent 5
5B55
...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (8 modules)
5C00
Neutral Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5C02
Neutral Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5C03
Neutral Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5C05
Neutral Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5C07
Neutral Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5C08
Neutral Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5C09
Reserved (8 items)
0 to 1
---
1
F001
0
5C11
...Repeated for Neutral Instantaneous Overcurrent 2
5C22
...Repeated for Neutral Instantaneous Overcurrent 3
5C33
...Repeated for Neutral Instantaneous Overcurrent 4
5C44
...Repeated for Neutral Instantaneous Overcurrent 5
5C55
...Repeated for Neutral Instantaneous Overcurrent 6
5C66
...Repeated for Neutral Instantaneous Overcurrent 7
5C77
...Repeated for Neutral Instantaneous Overcurrent 8
Ground Time Overcurrent (Read/Write Grouped Setting) (4 modules)
5D00
Ground Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5D01
Ground Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5D02
Ground Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5D03
Ground Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5D07
Ground Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5D09
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...