GE Multilin
C60 Breaker Protection System
6-15
6 ACTUAL VALUES
6.3 METERING
6
DELTA-CONNECTED INSTRUMENT TRANSFORMERS:
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
*
The power system voltages are phase-referenced – for simplicity – to
VAG
and
VAB
, respectively. This, however, is a
relative matter. It is important to remember that the C60 displays are always referenced as specified under
SETTINGS
SYSTEM SETUP
POWER SYSTEM
FREQUENCY AND PHASE REFERENCE
.
The example above is illustrated in the following figure.
Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS
•
ABC phase rotation:
•
ACB phase rotation:
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V *
VT
CONN.
RELAY INPUTS, SEC. V
SYMM. COMP, SEC. V
V
AG
V
BG
V
CG
V
AB
V
BC
V
CA
F5AC
F6AC
F7AC
V
0
V
1
V
2
13.9
∠
0°
76.2
∠
–125°
79.7
∠
–250°
84.9
∠
–313°
138.3
∠
–97°
85.4
∠
–241°
WYE
13.9
∠
0°
76.2
∠
–125°
79.7
∠
–250°
19.5
∠
–192°
56.5
∠
–7°
23.3
∠
–187°
UNKNOWN (only
V
1 and
V
2
can be determined)
84.9
∠
0°
138.3
∠
–144°
85.4
∠
–288°
DELTA
84.9
∠
0°
138.3
∠
–144°
85.4
∠
–288°
N/A
56.5
∠
–54°
23.3
∠
–234°
V_0
N/A
=
V_1
1
30
–
°
∠
3 3
--------------------
V
AB
aV
BC
a
2
V
CA
+
+
(
)
=
V_2
1 30
°
∠
3 3
-----------------
V
AB
a
2
V
BC
aV
CA
+
+
(
)
=
V_0
N/A
=
V_1
1 30
°
∠
3 3
-----------------
V
AB
a
2
V
BC
aV
CA
+
+
(
)
=
V_2
1
30
–
°
∠
3 3
--------------------
V
AB
aV
BC
a
2
V
CA
+
+
(
)
=
827844A1.CDR
A
B
C
WYE
VTs
1
0
2
A
B
C
DE
LTA VTs
1
2
SYST
E
M
V
OLTAG
E
S
SYMM
E
TR
I
CAL
COMPO
NEN
TS
UR phase angle
reference
UR phase angle
reference
UR phase angle
reference
UR phase angle
reference
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...