B-36
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
Field Unit Raw Data Actuals (Read Only) (8 modules)
4E00
Raw Field Data AC1 Mag
0 to 0.001
A
0.001
F003
0
4E02
Raw Field Data AC1 Angle
0 to 0.1
degree
0.1
F002
0
4E03
Raw Field Data AC2 Mag
0 to 0.001
A
0.001
F003
0
4E05
Raw Field Data AC2 Angle
0 to 0.1
degree
0.1
F002
0
4E06
Raw Field Data AC3 Mag
0 to 0.001
A
0.001
F003
0
4E08
Raw Field Data AC3 Angle
0 to 0.01
degree
0.1
F002
0
4E09
Raw Field Data AC4 Mag
0 to 0.001
A
0.001
F003
0
4E0B
Raw Field Data AC4 Angle
0 to 0.01
degree
0.1
F002
0
4E0C
Raw Field Data AC5 Mag
0 to 0.001
A/V
0.001
F003
0
4E0E
Raw Field Data AC5 Angle
0 to 0.01
degree
0.1
F002
0
4E0F
Raw Field Data AC6 Mag
0 to 0.001
A/V
0.001
F003
0
4E11
Raw Field Data AC6 Angle
0 to 0.01
degree
0.1
F002
0
4E12
Raw Field Data AC7 Mag
0 to 0.001
A/V
0.001
F003
0
4E14
Raw Field Data AC7 Angle
0 to 0.01
degree
0.1
F002
0
4E15
Raw Field Data AC8 Mag
0 to 0.001
A/V
0.001
F003
0
4E17
Raw Field Data AC8 Angle
0 to 0.01
degree
0.1
F002
0
4E18
Raw Field Data DC1
0 to 0.001
V
0.001
F002
0
4E19
Raw Field Data DC2
0 to 0.001
V
0.001
F002
0
4E1A
Raw Field Data DC3
0 to 0.001
V
0.001
F002
0
4E1B
Raw Field Data FCI States (2 items)
0 to 1
---
1
F500
0
4E1D
Raw Field Data SI States
0 to 1
---
1
F500
0
4E1E
Raw Field Data SI Test States
0 to 1
---
1
F500
0
4E1F
Raw Field Data Brick ADC Temperature
0 to 1
degree
1
F002
0
4E20
Raw Field Data Brick Transceiver Temperature
0 to 1
degree
1
F002
0
4E21
Raw Field Data Brick Transceiver Voltage
0 to 0.01
V
0.01
F001
0
4E22
Raw Field Data Brick Transceiver Current
0 to 1
mA
1
F001
0
4E23
Raw Field Data Brick Tx Power
0 to 0.1
dBm
0.1
F002
0
4E24
Raw Field Data Brick Rx Power
0 to 0.1
dBm
0.1
F002
0
4E25
Raw Field Data Brick Diagnostics (2 items)
0 to 65535
---
1
F500
0
4E27
Raw Field Data Local Transceiver Temperature
0 to 1
degree
1
F002
0
4E28
Raw Field Data Local Transceiver Voltage
0 to 0.01
V
0.01
F001
0
4E29
Raw Field Data Local Transceiver Current
0 to 1
mA
1
F001
0
4E2A
Raw Field Data Local Tx Power
0 to 0.1
dBm
0.1
F002
0
4E2B
Raw Field Data Local Rx Power
0 to 0.1
dBm
0.1
F002
0
4E2C
Repeated for Field Unit 2
4E58
Repeated for Field Unit 3
4E84
Repeated for Field Unit 4
4E80
Repeated for Field Unit 5
4EDC
Repeated for Field Unit 6
4F08
Repeated for Field Unit 7
4F34
Repeated for Field Unit 8
FlexLogic (Read/Write Setting)
5000
FlexLogic Entry (512 items)
0 to 4294967295
---
1
F300
2097152
RTD Inputs (Read/Write Setting) (48 modules)
5400
RTD Input 1 Function
0 to 1
---
1
F102
0 (Disabled)
5401
RTD Input 1 ID
---
---
---
F205
“RTD Ip 1“
5407
RTD Input 1 Type
0 to 3
---
1
F174
0 (100 ohm
Platinum)
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...