GE Multilin
C60 Breaker Protection System
5-113
5 SETTINGS
5.4 SYSTEM SETUP
5
•
SWITCH 1 MODE:
This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
•
SWITCH 1 OPEN:
This setting selects an operand that when activated, and unless blocked, initiates the disconnect
switch 1 open command.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents initiation of the disconnect switch 1 command.
This setting can be used for blocking disconnect switch opening for instance when switchyard monitoring indicates cur-
rent exceeding the switch's interrupting rating can be flowing through the switch.
•
SWITCH 1 CLOSE:
This setting selects an operand that when activated, and unless blocked, initiates the disconnect
switch 1 close command.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents initiation of disconnect switch 1 close com-
mands. This setting can be used for blocking disconnect switch closing, for instance to prevent closing into a closed
ground switch.
•
SWTCH 1
Φ
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input is for a normally-open 89/a status input that creates a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single 89/a
input as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”,
the input mentioned above is used to track phase A and the
SWITCH 1
Φ
B
and
SWITCH 1
Φ
C
settings select operands to
track phases B and C, respectively.
•
SWTCH 1
Φ
A/3P OPND:
This setting selects an operand, usually a contact input, that is for a normally-closed 89/b
status input that creates a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available,
then an inverted 89/a status signal can be used.
•
SWITCH 1
Φ
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
Φ
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
Φ
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
Φ
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 TOPERATE
: This setting specifies the required interval to overcome transient disagreement between the
89/a and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time
has expired, the
SWITCH 1 BAD STATUS
FlexLogic operand is asserted for alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
IEC 61850 functionality is permitted when the C60 is in “Programmed” mode and not in the local control mode.
NOTE
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...