GE Multilin
C60 Breaker Protection System
5-219
5 SETTINGS
5.7 CONTROL ELEMENTS
5
c) SPECIAL APPLICATION OF THE SYNCHROCHECK ELEMENT
The synchrocheck element is intended for applications where the potential sources are located on either side of the breaker
to be closed. It can also be used in cases where a power transformer is located between the two potential sources by com-
pensating for the power transformer phase shift with the auxiliary VT connection to the C60 and the auxiliary VT connection
setting, as shown in the following example for the 230/13.8 kV Yn/D-1 transformer.
Figure 5–96: SYNCHROCHECK APPLIED ACROSS A TRANSFORMER
In this example, the phase voltage VT input is programmed as "Delta" with a ratio of 14400 V / 120 V = 120 and with a sec-
ondary voltage setting of 13800 V / 120 = 115 volts. The auxiliary VT connection is selected to be VAB since this vector is in
phase with VA on the transformer 13.8 kV side. The auxiliary secondary voltage setting is 230000 V / (
√
3/2000) = 66.4 volts
and the auxiliary VT ratio is calculated as 2000 *
√
3 * 13.8 kV / 230 kV = 208. Note that auxiliary VT ratio is chosen to match
primary voltage on the 13.8 kV side, because synchrocheck is comparing voltages in primary volts. Therefore metered val-
ues for the auxiliary VT now reflect and are referenced to the AB voltage of the 13.8 kV side of the transformer.
Phase VT input
A
B
C
a
b
c
System nominal
Vpp = 13.8 kV
System nominal
Vpp = 230 kV
138000 : 69
14400 : 120
~5a
52
~5c ~6a ~6c ~7a ~7c
~8a
~8c
Auxiliary VT input
UR-series device
843808A2.CDR
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...