B-18
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Source Demand (Read Only) (4 modules)
1E00
Source 1 Demand Ia
0 to 999999.999
A
0.001
F060
0
1E02
Source 1 Demand Ib
0 to 999999.999
A
0.001
F060
0
1E04
Source 1 Demand Ic
0 to 999999.999
A
0.001
F060
0
1E06
Source 1 Demand Watt
0 to 999999.999
W
0.001
F060
0
1E08
Source 1 Demand Var
0 to 999999.999
var
0.001
F060
0
1E0A
Source 1 Demand Va
0 to 999999.999
VA
0.001
F060
0
1E0C
Reserved (4 items)
---
---
---
F001
0
1E10
...Repeated for Source 2
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
Source Demand Peaks (Read Only Non-Volatile) (4 modules)
1E80
Source 1 Demand Ia Maximum
0 to 999999.999
A
0.001
F060
0
1E82
Source 1 Demand Ia Maximum Date
0 to 4294967295
---
1
F050
0
1E84
Source 1 Demand Ib Maximum
0 to 999999.999
A
0.001
F060
0
1E86
Source 1 Demand Ib Maximum Date
0 to 4294967295
---
1
F050
0
1E88
Source 1 Demand Ic Maximum
0 to 999999.999
A
0.001
F060
0
1E8A
Source 1 Demand Ic Maximum Date
0 to 4294967295
---
1
F050
0
1E8C
Source 1 Demand Watt Maximum
0 to 999999.999
W
0.001
F060
0
1E8E
Source 1 Demand Watt Maximum Date
0 to 4294967295
---
1
F050
0
1E90
Source 1 Demand Var
0 to 999999.999
var
0.001
F060
0
1E92
Source 1 Demand Var Maximum Date
0 to 4294967295
---
1
F050
0
1E94
Source 1 Demand Va Maximum
0 to 999999.999
VA
0.001
F060
0
1E96
Source 1 Demand Va Maximum Date
0 to 4294967295
---
1
F050
0
1E98
Reserved (8 items)
---
---
---
F001
0
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker Flashover 1 Function
0 to 1
---
1
F102
0 (Disabled)
2197
Breaker Flashover 1 Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
2198
Breaker Flashover 1 Side 2 Source
0 to 6
---
1
F211
0 (None)
2199
Breaker Flashover 1 Status Closed A
0 to 4294967295
---
1
F300
0
219B
Breaker Flashover 1 Status Closed B
0 to 4294967295
---
1
F300
0
219D
Breaker Flashover 1 Status Closed C
0 to 4294967295
---
1
F300
0
219F
Breaker Flashover 1 Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
0 to 100000
V
1
F060
1000
21A2
Breaker Flashover 1 Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21A3
Breaker Flashover 1 Pickup Delay
0 to 65.535
s
0.001
F001
100
21A4
Breaker Flashover 1 Supervision Phase A
0 to 4294967295
---
1
F300
0
21A6
Breaker Flashover 1 Supervision Phase B
0 to 4294967295
---
1
F300
0
21A8
Breaker Flashover 1 Supervision Phase C
0 to 4294967295
---
1
F300
0
21AA
Breaker Flashover 1 Block
0 to 4294967295
---
1
F300
0
21AC
Breaker Flashover 1 Events
0 to 1
---
1
F102
0 (Disabled)
21AD
Breaker Flashover 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
21AE
Reserved (4 items)
---
---
---
F001
0
21B2
...Repeated for Breaker Flashover 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E0
Breaker 1 Arcing Current Phase A
0 to 99999999
kA
2
-cyc
1
F060
0
21E2
Breaker 1 Arcing Current Phase B
0 to 99999999
kA
2
-cyc
1
F060
0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E4
Breaker 1 Arcing Current Phase C
0 to 99999999
kA
2
-cyc
1
F060
0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (4 modules)
21E6
Breaker 1 Operating Time Phase A
0 to 65535
ms
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...