13-17-613 Page 69
Table 6-3: Shutdown Fault Definitions Cont.
Shutdown Condition
Description
Action
Open TT3
Connection to thermistor TT3 is
open
Check wiring between thermistor
TT3 and controller
Open XD1
Connection to pressure transducer
PT1 is open
Check wiring between pressure
transducer PT1 and controller
Open XD2
Connection to pressure transducer
PT2 is open
Check wiring between pressure
transducer PT2 and controller
Open XD3
Connection to pressure transducer
PT3 is open
Check wiring between pressure
transducer PT3 and controller
Power Failure
Low voltage on 24V input to
controller
Check DC power supply and line
voltage stability
Shorted TT1
Connection to thermistor TT1 is
shorted
Check wiring between thermistor
TT1 and controller
Shorted TT2
Connection to thermistor TT2 is
shorted
Check wiring between thermistor
TT2 and controller
Shorted TT3
Connection to thermistor TT3 is
shorted
Check wiring between thermistor
TT3 and controller
Shorted XD1
Connection to pressure transducer
PT1 is shorted
Check wiring between pressure
transducer PT1 and controller
Shorted XD2
Connection to pressure transducer
PT2 is shorted
Check wiring between pressure
transducer PT2 and controller
Shorted XD3
Connection to pressure transducer
PT3 is shorted
Check wiring between pressure
transducer PT3 and controller
Hardware Fault
Controller hardware failure
detected.
Check controller for malfunction or
damage.
SD Card Error
SD card failure
Check SD card is inserted into
controller correctly
Configuration Error
Configuration failure
Reload configuration files into
controller using SD card
Can Comm Error
Communications failure between
control and IO module
Check all wire connections on
controller and IO module
Seq Comm Error
Communications failure between
sequenced machines
Check all wire connections on
controllers
Drive 1 Comm Error
Communications failure between
controller and drive 1
Check all wire connections
between controller and drive 1
Drive 2 Comm Error
Communications failure between
controller and drive 2
Check all wire connections
between controller and drive 2
Drive 3 Comm Error
Communications failure between
controller and drive 3
Check all wire connections
between controller and drive 3
Drive 1 Fault
Drive 1 failure detected
Check drive 1 for malfunction or
damage
Drive 2 Fault
Drive 2 failure detected
Check drive 2 for malfunction or
damage
Drive 3 Fault
Drive 3 failure detected
Check drive 3 for malfunction or
damage
DIN VFD Fault
Digital input for VFD has tripped
Check wires connected to input;
check VFD
DIN MBC Fault
Digital input for MBC has tripped
Check wires connected to input;
check MBC
DIN Safety Switch
Digital input for the safety switch
has tripped
Check safety switch wiring
DIN Belt Break
Digital Input for a belt break has
tripped
Check wires connected to input;
check belt
High Interstage Pres
Interstage Pres > alarm set point
Check Interstage pressure and for
sources of high pressure