13-17-613 Page 37
5.1.6.5 Plant Pressure Timeout
Accessibility
Maintenance
Distributor
Factory
The next item in the
Operating Limits
menu is the
Plant Pressure Timeout
setting, which controls
the length of time the plant delivery pressure value may remain under the
Target Pressure
setting
before generating an advisory.
Note:
Setting this parameter to zero will disable the Plant Pressure Advisory.
Min Value: 0 seconds
Max Value: 600 seconds
Default Value: 180 seconds
5.1.6.6 Minimum Target Temperature
Accessibility
Maintenance
Distributor
Factory
The
Minimum Target Temperature
setting under the
Operational Limits
menu establishes the lower
temperature limit of the oil temperature control system on compressor packages with a Precision
Mixing Valve installed.
Note:
This parameter has no effect on packages that do not utilize a Precision Oil Mixing Valve.
5.1.6.1 Minimum Target Pressure
Accessibility
Maintenance
Distributor
Factory
The
Minimum Target Pressure
setting under the
Operational Limits
menu sets the lowest value
that the controller will allow the
Target Pressure
to be set to.
5.1.6.2 Inlet Temperature
Accessibility
Maintenance
Distributor
Factory
The
Inlet Temperature
setting is the next item under the
Operational Limits
menu. The
Inlet
Temperature
setting is used when there is an inlet temperature sensor on the package. When the
inlet temperature exceeds the set point of the inlet temperature limit, it will engage the inlet
temperature speed limiter.
5.1.6.3 VS Capacity Limit
Accessibility
Maintenance
Distributor
Factory
The
VS Capacity Limit
setting under the
Operational Limits
menu sets the percentage that the
controller will allow a variable speed machine to run at. For example, if the VS capacity limit is set at
90%, then the compressor will allow the VFD to run up to 90% of full speed.