13-17-613 Page 35
5.1.5 Current Date/Time
Accessibility
Maintenance
Distributor
Factory
The
Current Date/Time
category under the
Operational Settings
menu allows the user to change the
Date and Time settings, which are kept by the battery-backed real time clock on the AirSmart G2
Controller. This clock is used for timestamps on logging data such as notices and trend data, as well as
for AutoRun scheduling. The current date and time is displayed on the home screen and should be
adjusted if not correct.
The date and time format reads as follows:
hh:mm:ss
MM-DD-YYYY
Where:
MM = Month
DD = Day of Month
YYYY =Four-digit Year)
hh = Hour (using 24 hour clock)
mm = Minute
To set the current date and time:
1. Select the
Current Date/Time
option under the
Operational Settings
screen. Then select
Edit
Time
or
Edit Date.
This will trigger a numeric keypad set to enter a value in date or time
format.
2. Select
CLR
to clear the current value, and begin entering the desired setting in the format
MMDDYY
for date and
hhmmss
for time without punctuation. For example, 1-19-2014 would
be entered as 011914 and 15:11:00 would be entered as 151100.
3. Press
Enter
to commit the value and return to the
Current Date/Time
screen and verify that
the date and time are accurate.
5.1.6 Operating Limits
The
Operating Limits
menu allows the user to set Advisory and Shutdown conditions when specified
pressure and temperature thresholds are met. There are nine categories that can be set that include
plant pressure, discharge temperature, control box temperature, ambient temperature, plant pressure
timeout, min target temperature, min target pressure, inlet temperature, and VS capacity limit.
The
Operating Limits
menu structure is organized as follows: