13-17-613 Page 61
Figure 5-22: Core DOUT Test
5.4.8 Multi-Machine Sequencing
Accessibility
Maintenance
Distributor
Factory
The next item in the
Machine Configuration
menu is the
Multi-Machine Sequencing
menu. This menu
allows the distributor and factory user to configure multiple machines so that they are sequenced
together. The parameter that can be set in this menu are capacity, number of units, unit number,
transfer interval, lag start delay, transfer load increment, transfer load decrement, and sequence time
offset. See the
AirSmart G2 Sequencing Manual (13-17-615)
for detailed information on sequencing
operation.
The
Multi-Machine Sequencing
menu structure is organized as follows:
5.4.8.1 Capacity
Accessibility
Maintenance
Distributor
Factory
Capacity
is used to decide which compressor will become the Leader in the sequence. Normally the
largest compressor will be the Leader unless multiple compressors of the same capacity are present
in the network, in which the compressors will use total hours to calculate Leader control.
5.4.8.2 Number of Units
Accessibility
Maintenance
Distributor
Factory
The
Number of Units
is a value that should be set to the factory value.