13-17-613 Page 48
5.4.2.1 Starter Type
Accessibility:
Maintenance
Distributor
Factory
The
Starter Type
menu displays what starter unit variation is implemented in the current machine.
The starter type will be one of full voltage, wye delta, or none.
5.4.2.2 VFD
Accessibility
Maintenance
Distributor
Factory
The next item in the
Drive Train
menu is the
VFD
menu. The
VFD
menu allows the user to configure
the settings for the VFDs in variable speed compressor packages.
The
VFD
menu structure is organized as follows:
5.4.2.2.1 Cold Start Timer
Accessibility
Maintenance
Distributor
Factory
The first item in the
VFD
menu is the
Cold Start Timer
. The
Cold Start Timer
parameter sets the
time the compressor will run at a specified capacity when the inlet temp of the compressor reads a
value that is less than 50 degrees Fahrenheit.
5.4.2.2.2 Cold Start Capacity
Accessibility
Maintenance
Distributor
Factory
The next item in the
VFD
menu is the
Cold Start Capacity
. The
Cold Start Capacity
parameter
sets the capacity limit the compressor will run at for a specified time when the inlet temp of the
compressor reads a value that is less than 50 degrees Fahrenheit. For example, when the
compressors inlet temp reads a value less than 50 degrees Fahrenheit and the
cold start
capacity
is set at 90%, the compressor will run at 90% of full speed for the duration of the
cold
start timer
.
5.4.2.2.3 System Voltage
Accessibility
Maintenance
Distributor
Factory
The next item in the
VFD
menu is the
System Voltage
. The
System Voltage
parameter sets the
voltage of the VFD. This voltage will depend on the system configuration of the machine.