13-17-613 Page 47
5.4.1.4 Oil Type
Accessibility
Maintenance
Distributor
Factory
The next item in the
Compressor Menu
selects the
Oil Type
. The
Oil Type
setting determines how
fast the
Oil Change Timer
will count down as the compressor discharge temperature rises as
shown in the table below. The
Oil Type
selections are as follows.
Default Value: Compressor model dependent
·
Standard
: Oil Change Timer counts down normally at high temperature. Use with AEON
9000SP or similar lubricant.
·
High Temp
: Oil Change Timer counts down more slowly at high temperature. Use with
AEON 9000TH or similar lubricant.
·
Food Grade
: Oil Change Timer counts down at same rate as Standard Oil. Use with AEON
6000FG or similar lubricant.
Table 5-1: Oil Change Multipliers
Oil Aging Clock
Multiplier
Standard/Food Grade Oil
Temperature Break Points
High Temp Oil
Temperature Break Points
X 1
< 180
°
F (82
°
C)
< 210
°
F (99
°
C)
X 1.3
180
°
F - 189
°
F (82
°
C - 87
°
C)
210
°
F - 219
°
F (99
°
C - 104
°
C)
X 2
190
°
F - 198
°
F (88
°
C - 92
°
C)
220
°
F - 228
°
F (104
°
C - 109
°
C)
X 4
199
°
F - 216
°
F (93
°
C - 102
°
C)
> 229
°
F (109
°
C)
X 8
217
°
F - 234
°
F (103
°
C - 112
°
C)
X 16
> 234
°
F (112
°
C)
5.4.2 Drive Train
The
Drive Train
menu
gives the user access to the configuration of the motor drive configuration on the
system. This includes the starter type and timings as well as motor currents and related information.
Note:
Motor information such as voltage, currents, power, and service factor amps are not utilized and
should be ignored for fixed speed machines which do not include a current transducer.
The
Drive Train
menu structure is organized as follows: