U41261-J-Z816-4-76
71
3.3 Preparations for Operation
l
Install the PRIMEPOWER850 rack-mount type (16U) server away from EM noise
generating devices such as photocopiers, air conditioners, or welders.
l
Take electrostatic prevention measures. Note that many carpets generate static
electricity that can cause the PRIMEPOWER850 rack-mount type (16U) server to
malfunction.
l
When moving the PRIMEPOWER850 rack-mount type (16U) server, do not pull
on the front cover. This could cause damage to the unit.
3.3.2
Installation specifications
lists the installation specifications of the PRIMEPOWER850 rack-mount
type (16U) server.
Table 3.5 Installation specifications of the PRIMEPOWER850 rack-mount type
(16U) server (1/3)
Item
Specifications
(Model name: PW0VCRyyyx,
PW0VDRyyyx, PW0VFRyyyx,
PW0VGRyyyx) (Note 2)
(Model name: PW0V0CR1x,
PW0V0CR6x, PW0V0DR1x,
PW0V0DR6x, PW0V0AR2x,
PW0V0AR7x)
Weight (Note 1)
160 kg (352.8 lb.) (maximum )
Power
supply
Input voltage
Single phase, 200 to 240 VAC (+10%)
Input frequency 50/60 Hz (+2 / -4 %)
Input Power 1 SB (8CPU)
2400 VA
2000 VA
2 SB (16CPU)
3900 VA
3500 VA
Maximum
current
consumption
1 SB (8CPU)
12.0 A
10.0 A
2 SB (16CPU)
19.5 A
17.5 A
Leakage current
Less than 5.0 mA (per cable)
Ground resistance
Less than 100
Ω
Note 1: Not including the rack-mount rails and the maintenance tray
Note 2: In model names, x is any letter from A to Z. And y is any letter from A to Z
or any digit from 0 to 9.
Содержание PRIMEPOWER650
Страница 1: ...Edition September 2004 PRIMEPOWER850 650 ...
Страница 22: ......
Страница 30: ......
Страница 81: ...U41261 J Z816 4 76 51 2 5 Configuring for the Fast Memory Mode ...
Страница 82: ......
Страница 154: ......
Страница 162: ......
Страница 172: ......
Страница 180: ......
Страница 192: ......
Страница 194: ......