PARAMETER REFERENCE TABLES
Parameter Descriptions > Protection Menu
222
PROT-18 1042 Y OH Warning
0.0 to 110.0 °C
Set Heat Sink Over Heat Warning level. When temperature exceeds 110 °C,
the drive stops with an IGBT over-heat fault. Cooling fan is activated when
temperature reaches 15 °C less than value. The cooling fan deactivates for
35 °C less than value.
PROT-19 1043 Y PTC/PT100 Sel
0_Alarm and Run
1_Trip Decel Stop
2_Trip Coast Stop
3_Disabled
Set operation when PTC, PT100, or KTY84 exceed level 2.
PROT-20 1044 Y PTC Level
0.0 to 100.0%
Set detection level of PTC. The corresponding value for 100% is the analog
input maximum value
PROT-21 1045 Y OPO Trip
0_Alarm and Run
1_Trip Decel Stop
2_Trip Coast Stop
3_Disabled
Output Phase Open Trip: Select operation for Output Phase Loss.
PROT-22 1046 Y OPO Delay
0.000 to 65.535 sec
Duration of output phase loss until operation occurs.
PROT-23 1047 Y OPO Current
0.00 to 100.00%
Set level of output phase loss.
PROT-24 1048 Y OPO Decel
0.000 to 65.535 sec
DC Brake Time of output phase loss.
PROT-25 1049 Y LvX Auto Reset
0_Disable
1_Enable
Low Voltage Extension of faults Auto Reset: Set low voltage fault opera
-
tion to auto reset. Once DC bus voltage returns, the VFD clears fault and
restarts motor.
PROT-26 1050 Y IPO Check Time
0.0 to 600.00 sec
Input Phase Open Check Time: Set how often to check for input phase loss.
PROT-27 1051 Y IPO Ripple
(Varies with VFD rating)
An input phase loss is detected when DC bus ripple is higher than IPO Rip
-
ple for duration of
IPO Check Time [PROT-26]
plus 30 seconds.
PROT-28 1052 Y IPO Trip
0_Alarm and Decel
1_Alarm and Coast
Operation when input phase loss is detected.
PROT-29 1053 Y Derating Type
0_Carrier by I_T
1_Limit Current
2_Limit Carrier
Set how the VFD derates itself.
0_Limit the carrier wave to reach max load current and temperature.
1_Limit the current to use max carrier frequency.
2_Limit the carrier wave to reach max load current and temperature except
when output current is the derating ratio x 130% of output current in light
load.
PROT-30 1054 Y PT100 Level 1
-20.0 to 99.9 °C
Level the PT100 reaches for duration for
PT100 L-1 Delay [PROT-33]
causing
drive to back frequency down to
PT100 L-1 Freq [PROT-32]
.
PROT-31 1055 Y PT100 Level 2
60.1 to 200 °C
Level the PT100 reaches causing
PTC Select [PROT-19]
operation.
PROT-32 1056 Y PT100 L-1 Freq
0.0 to 599 Hz
Frequency the VFD reduces to after reaching
PT100 Level 1 [PROT-30]
for dura
-
tion of
PT100 L-1 Delay [PROT-33]
.
PROT-33 1057 Y PT100 L-1 Delay 0 to 6000 sec
Duration PT100 has to be above
PT100 Level 1 [PROT-30]
to cause frequency
reduction to
PT100 L-1 Freq [PROT-32]
.
PROT-34 1058 Y Gnd Fault Level
0.0 to 6553.5%
Percentage of light-load current that current phase unbalance has to reach
for duration of
Gnd Fault Delay [PROT-35]
for ground fault to occur.
PROT-35 1059 Y Gnd Fault Delay 0.0 to 6553.5 sec
Duration of current phase unbalance for ground fault to occur.
PROT-36 1060 Y STO Alarm Type 0_STO Latching
1_STO Non-Latch
0_When VFD triggers STO protection it will require reset.
1_When STO is triggered and then connection restored, VFD will be ready
to operate.
PROT-37 1061 Y IPF S-Search
0_Disable
1_At Last Freq
2_At Min Freq
Speed search treatment after Instantaneous Power Failure (IPF).
PROT-38 1062 Y Max IPF Time
0.0 to 20.0 sec
Max Instantaneous Power Failure Time: Duration power loss has to occur
for output to be turned off (coast stop).
PROT-39 1063 Y SS Current Lmt
20 to 200%
Speed Search Current Limit: Following a momentary power loss, the drive
will start speed search operation if the output current is greater than
[PROT-
39]
value.
PROT-40 1064 Y SS After Fault
0_Disable
1_At Last Freq
2_At Min Freq
Speed search operation after fault.
PROT-42 1066 Y SS Normal Start 0_Disable
1_At Max Freq
2_At Start Freq
3_At Min Freq
Speed search operation at normal start.
CODE Mod
Bus AR Display Name
Range
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...