MAINTENANCE
Troubleshooting
190
PLSF
(60)
Scan time fail
PLC scan time exceeds the maximum allowable time
Action and Reset
Action condition
The PLC scan time exceeds the maximum allowable time (400 ms)
Action time
Immediately
Reset method
Check if the program is correct and re-download the program
Reset condition
N/A
Recorded
N/A
Possible Causes
Corrective Action
• The PLC scan time exceeds the
maximum allowable time (400ms)
• Check if the source code is correct and re-download the program.
Warning Display
Description
PLSn
(56)
Check sum error
PLC checksum error
Action and Reset
Action condition
PLC checksum error is detected after power on, then PLSn warning shows
Action time
Immediately displays when the fault is detected
Reset method
Automatically
Reset condition
Check if the program is correct and re-download the program. If the fault does not exist, the warning clears.
Recorded
N/A
Possible Causes
Corrective Action
• The program detects checksum error
during PLC operation
• Disable PLC
• Remove PLC program (
[ADV-03]
= 6)
• Enable PLC
• Re-download PLC program
Warning Display
Description
PLSv
(51)
Save mem defect
Data error during PLC operation
Action and Reset
Action condition
The program detects incorrect written address (e.g. the address has exceeded the range) during PLC operation
Action time
Immediately
Reset method
Check if the program is correct and re-download the program
Reset condition
Automatically
Recorded
N/A
Possible Causes
Corrective Action
• An incorrect written address is detected
during PLC operation
• Make sure the write-in address is correct and re-download the program.
Warning Display
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...