OPERATION
Control Options
76
Lubrication Relay
The VFD has the capability to automatically activate a lubrication solenoid for line shaft turbine pumps. For
industrial machines with an external lubrication supply, it can also activate it before starting the motor.
Timers are available to enable lubrication before, during, and/or after running the motor, in any combina
-
tion.
To enable the lubrication function, set the following parameters:
Lubrication Output Relay [IO–47] through [IO-49]:
Use one of the Relay Outputs (RA1–RA3), and set the
corresponding parameter to
41_Lube/S-Clean
.
Lube/S-Clean [IO–41]:
Select
1_Lubrication
.
Pre-Lube Timer [IO–43]:
This setting determines relay activation time after a run command is received and
before the VFD starts. When the timer expires, the lubrication relay will be deactivated and the VFD will
start the motor. If a stop command is received or the VFD trips during Pre-lubrication, the relay will be deac
-
tivated.
Run-Lube Timer [IO–44]:
This setting determines relay activation time while the VFD is running.
•
When set to a value greater than 0 and less than 6000, the relay will be activated at VFD start and will
deactivate when the timer expires. If the VFD stops while the timer is active, the relay will deactivate.
•
If the timer is set to the maximum 6000 sec, the relay will be activated during run mode until the VFD
stops (no timing). If the VFD stops or trips, the relay will deactivate.
Post-Lube Tmr [IO–45]:
This setting determines relay activation time after the VFD comes to a stop (0 Hz).
Screen Clean Relay
When water is pumped from a lake or pond, the suction screen requires periodic cleaning. The VFD can
automate this process by providing a relay output to an external solenoid valve that will discharge pressur
-
ized water to clean the screen. This feature works only in run mode in HOA Hand or Auto.
The VFD provides a one minute (non-adjustable) cleaning pulse at every start. When the cleaning pulse is
done, the
S-Clean Timer [IO–42]
starts. When the timer expires, another cleaning pulse is activated. This cycle
continues until the VFD stops.
To enable the Clean Screen function, set the following parameters:
Screen Clean Output Relay [IO–47] through [IO-49]:
Use one of the Relay Outputs (RA1–3), and set the
corresponding parameter to
41_Lube/S-Clean
.
Lube/S-Clean [IO–41]:
Select
2_Screen Clean
.
S-Clean Timer [IO–42]:
Time between cleaning pulses.
Clean Pump/Anti Jam (De-ragging and impeller cleaning)
In de-watering and wastewater pump applications, the Clean Pump feature will provide periodic (set by
Clean Pump Tmr [ADV2-56]
) fast ramping starts to clean the impeller. VFD will ramp up to half speed and run for
5 seconds in Forward direction during VFD stop mode with a “Clean Pump” message. This will prevent the
accumulation settling in the pump and impeller.
NOTE:
The Clean Pump feature only works in Auto mode when a run command is removed by DI, AI
Trigger or Comms (Sleep mode excluded).
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...