PARAMETER REFERENCE TABLES
Parameter Descriptions > Option Menu
228
Option-06 1798 N Relay exp. RA10 0_No Function
1_Run
2_FDT-1
3_FDT-2
4_FDT-3
5_FDT-4
6_FDT-5
7_Drive ready
8_Fault
9_VFD Overheat
10_DC Brake
11_PID F/B Loss
12_Counter Done
13_Pre-Count Done
14_Alarm
15_FWD CMD
16_REV CMD
17_Analog Trigger
19_Overcurrent 2
20_High Load
21_Under Load
22_Fireman O-ride
23_Bypass
24_Motor-1 Out
25_Motor-2 Out
26_Motor-3 Out
27_Motor-4 Out
28_Motor-5 Out
29_Motor-6 Out
30_Motor-7 Out
31_Pipe Leak
32_Preheat Output
33_Steady
34_Pre-PID
35_Sleep
36_Speed Search
37_Pipe Broken
38_Damper Output
39_Aux Timer Out
40_Overpressure
41_Lube/S-Clean
42_ACI Loss
43_AVI1 Loss
44_Hand Mode
45_Auto Mode
47_MMC Out
48_Jockey Pump
49_At High Current
50_At Low Current
RA1 Default = Fault
1_During Run Mode
2_When frequency reference value is achieved
3_On above
[IO-52]
freq and Off below
[IO-52]
-
[IO-53]
freq
4_On above
[IO-54]
freq and Off below
[IO-54]
+
[IO-55]
freq
5_On up to FDT-4/5 freq
6_On above FDT-4/5 freq
7_When drive is powered and ready (no faults)
8_When drive has tripped on any fault
9_When VFD temperature reaches trip level
10_When DC injection brake is activated
11_When PID feedback source signal value is abnormal
12_When pulse counter achieves the counter set-value
13_When pulse counter achieves pre-count value
14_When alarm is triggered by any alarm condition
15_When VFD operates in Forward direction
16_When VFD operates in Reverse direction
17_When analog signal reaches a trigger level
19_When VFD trips on Overcurrent 2
20_HLD triggered
21_ULD triggered
22_When Fireman’s Override mode is activated
23_When drive switches from Soft-Start mode to Bypass
24_When Motor-1 is enabled in MMC control
25_When Motor-2 is enabled in MMC control
26_When Motor-3 is enabled in MMC control
27_When Motor-4 is enabled in MMC control
28_When Motor-5 is enabled in MMC control
29_When Motor-6 is enabled in MMC control
30_When Motor-7 is enabled in MMC control
31_Pipe Leak protection is triggered
32_VFD provides Motor Preheat output
33_VFD provides steady frequency output
34_VFD is in Pipe Fill mode
35_VFD is in Sleep mode
36_VFD is in Speed Search mode
37_Pipe Broken protection is triggered
38_When Damper motor output is activated
39_Auxiliary timer output
40_Overpressure is triggered
41_When Lube or Screen Clean solenoid output is activated
42_When ACI analog input signal value is abnormal
43_When AVI1 analog input signal loss is detected
44_When VFD control is in Hand mode
45_When VFD control is in Auto mode
47_Aux motor start output in MMC control
48_Jockey pump start output
49_When current reaches High Current trigger level
50_When current is below Low Current trigger level
Option-07 1799 N Relay exp. RA11
See
[Option-06]
Defines functionality of output relay RA11 on I/O extension card.
Option-08 1800 N Relay exp. RA12 See
[Option-06]
Defines functionality of output relay RA12 on I/O extension card.
Option-09 1801 N Relay exp. RA13 See
[Option-06]
Defines functionality of output relay RA13 on I/O extension card.
Option-10 1802 N Relay exp. RA14 See
[Option-06]
Defines functionality of output relay RA14 on I/O extension card.
Option-11 1803 N Relay exp. RA15 See
[Option-06]
Defines functionality of output relay RA15 on I/O extension card.
Option-12 1804 N Relay exp. RA16 See
[Option-06]
Defines functionality of output relay RA16 on I/O extension card.
Option-13 1805 N Relay exp. RA17 See
[Option-06]
Defines functionality of output relay RA17 on I/O extension card.
Option-14 1806 N Relay exp. RA18 See
[Option-06]
Defines functionality of output relay RA18 on I/O extension card.
Option-15 1807 N Relay exp. RA19 See
[Option-06]
Defines functionality of output relay RA19 on I/O extension card.
Option-16 1808 N Relay exp. RA20 See
[Option-06]
Defines functionality of output relay RA20 on I/O extension card.
CODE
Mod
Bus AR Display Name
Range
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...