ADVANCED APPLICATION OPTIONS
Dual PID Loop Control
103
Dual PID Loop Control
Balancing Pressure in Large Systems Using Multiple Pumps
Booster pumps connected in series in long pipe systems and controlled by VFDs can be set for automatic
pressure balancing without the need for communication.
Each pump has its own VFD with suction (ST) and discharge (PT) pressure transducers. When there is a long
distance between pumps, the discharge pressure at any one pump will typically be greater than the suction
pressure at the next pump.
•
The discharge side is programmed as a standard constant pressure PID loop (PID 1). Refer to
Operation with PID Feedback Control” on page 69
•
The suction side transducer is installed and programmed as an Auxiliary input in inverse mode (PID 2).
When suction pressure of PID 2 is at or above its setpoint
[ADV2–38]
, normal VFD operation will be main
-
tained using the PID 1 loop.
When pump 1 suction pressure drops below PID 2 setpoint because of inadequate water supply, PID 1 High
Freq Limit will be decreased to reduce flow, prevent cavitation, and prolong pumping time. The pump 1 dis
-
charge pressure will drop and VFD2 will decrease its High Freq Limit and VFD3, etc. will follow. In this way,
all pumps will act the same without any communication between them.
To enable this feature, set the following parameters:
AUX AI Select [ADV2–58]:
Select the terminal (
AVI1, AVI2, ACI
) with the PID 2 transducer connection. Set unit
type and scaling in
[ADV2-59]
to
[ADV2-61]
.
PID2 Output [ADV2–36]:
This parameter should be set to
1_Limit 1
P
st
P
PID
.
PID2 Type [ADV2–37]:
This parameter should be set to
1_PID Inverse
for this application.
PID2 Setpoint [ADV2–38]:
Desired suction pressure.
PID2 P-Gain [ADV2–39]:
Set the proportional gain value for PID2 operation. Default = 30%
PID2 I-Gain [ADV2–40]:
Set the integral gain value for PID2 operation. Default = 1 second.
PID2 Low Limit [ADV2–41]:
Set the minimum frequency for PID2 output. Range =
[SET–22]
to
[ADV2–42].
PID2 High Limit [ADV2–42]:
Set the maximum frequency for PID2 output. Range =
[ADV2–41]
to
[SET–23].
Pump 1
Pump 2
Pump 3
PT1-PT3 are Discharge Pressure Transducers (PID 1)
ST1-ST3 are Suction Pressure Transducers (PID 2)
ST1
PT1
ST2
PT2
ST3
PT3
70 PSI
70 PSI 40 PSI
70 PSI 40 PSI
40 PSI
VFD-1
VFD-2
VFD-3
X-Drive
X-Drive
X-Drive
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...