PARAMETER REFERENCE TABLES
Parameter Descriptions > ADVANCE Menu
217
ADV-06 0774 Y Acc/Dec Type
0_Linear Acc/Dec
1_Auto Acc/L-Dec
2_L-Acc/Auto Dec
3_Auto Acc/Dec
4_Lin, Auto Stall
Provides automated acceleration and deceleration with stall prevention.
0_Linear Acc/Dec: Accelerates and decelerates according to the setting of
[SET-11] ~ [SET-12]
and
[VFD-19] ~ [VFD-24]
.
1_Auto Acc/L-Dec: Auto detects the load torque and accelerates for the
fastest acceleration time and smoothest start current. Deceleration is linear
according to setting of
[SET-11] ~ [SET-12]
and
[VFD-19] ~ [VFD-24]
.
2_L-Acc/Auto Dec: Linear acceleration according to setting
[SET-11] ~ [SET-12]
and
[VFD-19] ~ [VFD-24]
. Auto detects the load re-generation and stops the
motor smoothly with the fastest decel time.
3_Auto Acc /Dec: Auto detects load for smoothest operation for accelera
-
tion and deceleration.
4_Lin, Auto Stall: Stall prevention by auto accel./decel being limited by
[SET-11] ~ [SET-12]
and
[VFD-19] ~ [VFD-24]
.
ADV-07 0775 N Acc/Dec Format 0_Unit 0.01 sec
1_Unit 0.1 sec
Precision of acceleration and deceleration time
ADV-08 0776 Y Energy Saving
0_Disabled
1_Enabled
When the output frequency is constant, the output voltage will auto
decrease to decrease power consumption.
ADV-09 0777 Y E-Saving Gain
10 to 1000%
Determines speed of adjusting output voltage in relationship to load reduc
-
tion. If the motor oscillates or has a quick temperature rise, the value should
be increased.
ADV-10 0778 N MMC Mode
0_Disabled
1_Equal Run Time
2_Soft Start mode
3_Lead-Lag
4_Run Time Alt
5_Rotate Lead
Type of operation for Multi-Motor Control.
NOTE:
3_Lead-Lag is the most common multi-pump control mode.
ADV-11 0779 N Motor Quantity
1 (default) to 7
Number of motors in MMC relay control setup. Limit is 3 without I/O card.
When I/O card is installed, selections 1 to 7 are available.
ADV-12 0780 N Aux Mtr Stop Hz 0 to
[SET-23]
Auxiliary Motor Stop Hertz: When output frequency is less than value and
remains for duration of
[ADV-15]
, motors will be shut down one by one.
ADV-13 0781 N Alt Run Time
0 to 60000 min
Duration of running a motor before switching to another motor.
ADV-14 0782 N S-Start ON Dly
0 to 3600 sec
Delay time before switching motor from VFD to power line.
ADV-15 0783 N S-Start Off Dly
0 to 3600 sec
Delay time before switching motor from power line to VFD.
ADV-16 0784 Y Mtr Switch Tmr
0 to 3600 sec
When timer expires, the system will start preparing to switch motors.
ADV-17 0785 Y Mtr Switch Hz
[SET-22]
to
[SET-23]
(Hz)
When the output frequency reaches value, the system will start preparing to
switch motors.
ADV-18 0786 Y Lag Start Freq
[ADV-23]
to
[SET-23]
Running above this frequency is one of the conditions for starting Lag
pump. Lag Start Frequency parameter is used for
[ADV-10]
selection
3_Lead-Lag MMC
control. Default= 59.50Hz.
ADV-19 0787 Y Lag Start Delay
0 to 600 sec
Sets a delay time to start Lag pump when both frequency and pressure con
-
ditions are met.
ADV-20 0788 Y Lag Start Level
0.1 to 10%
Sets percentage of
PID F/B Max [SET-20]
value to determine MMC Below Set
-
point level for Lag pump starting. This parameter is used for
[ADV-10]
selec
-
tion
3_Lead-Lag MMC
control.
ADV-21 0789 Y Lead Freq Drop
0.0 to
[SET-23]
(Hz)
PID High Frequency Limit drop value with
MMC Decel Time [ADV-22]
at Lag
pump start to prevent system overpressure condition. This parameter is
used for
[ADV-10]
selection
3_Lead-Lag MMC
control.
ADV-22 0790 Y MMC Decel Time 0 to 600 sec
Sets deceleration time for PID High Frequency limit value change from
High
Freq Limit [SET-23]
to (
[SET-23]
-
[ADV-21]
) at Lag pump start. This parameter is
used for
[ADV-10]
selection
3_Lead-Lag MMC
control.
ADV-23 0791 Y Lag Stop Freq
[SET-22]
to
[ADV-18]
(Hz)
Running below this frequency is one of the conditions for stopping Lag
pump. This parameter is used for
[ADV-10]
selection
3_Lead-Lag MMC
control.
ADV-24 0792 Y Lag Stop Delay
0 to 600 sec
Sets delay time to stop Lag pump when both frequency and pressure condi
-
tions are met. This parameter is used for
[ADV-10]
selection
3_Lead-Lag MMC
control.
ADV-25 0793 Y Lag Stop Level
0.1 to
[ADV-20]
(%)
Sets percentage value of
PID F/B Max [SET-20]
value to determine MMC At Set
-
point level for Lag pump stopping. This parameter is used for
[ADV-10]
selec
-
tion
3_Lead-Lag MMC
control.
CODE Mod
Bus AR Display Name
Range
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...