PARAMETER REFERENCE TABLES
Parameter Descriptions > I/O Menu
209
Parameter Descriptions > I/O Menu
AR = Adjustable while running.
VFD-46
(Cont.)
0302 N ID Code
686_265HP (200kW), 690V
687_333HP (250kW), 690V
Displays the identity code of the VFD (Read Only).
VFD-47 0303 N VFD Rated Amps (Variable)
Current rating of drive with respect to Light Duty and Normal Duty
[VFD-35]
(Read Only).
VFD-49 0305 N Firmware Version (Variable)
VFD software version (Read Only).
VFD-50 0306 Y Disp Filter A
0.001 to 65.535 sec
Minimizes the current fluctuation displayed by digital keypad.
VFD-51 0307 Y Disp Filter KPD
0.001 to 65.535 sec
Minimizes the display value fluctuation displayed by digital keypad.
VFD-52 0308 N FW Date
(Variable)
VFD software version date (Read Only).
VFD-53 0309 Y JOG ACC Time
0.0 to (variable) sec
Acceleration time in jog operation to increase frequency to jog frequency.
VFD-54 0310 Y JOG DEC Time
0.0 to (variable) sec
Deceleration time in jog operation to decrease frequency to 0Hz.
VFD-55 0311 Y JOG Frequency
0.0 to 600 Hz
Frequency commanded for jog operation.
VFD-56 0312 N Zero-speed Mode 0_Standby
1_Hold by DC Brake
2_Min Frequency
When commanded frequency is less than frequency min:
0_VFD stays at 0Hz.
1_Apply DC Brake by minimum voltage
2_VFD runs motor at minimum frequency.
VFD-57 0313 Y Power-on Start
0_Disable
1_Enable
When enabled, the VFD will automatically initiate operation after powered-
on with run command.
VFD-58 0314 Y H-Carrier Pitch
2 to 100 ms
A time setting for duration of each frequency segment in Hopping Carrier
cycle.
VFD-60 0316 N V/F F-Point 1
Variable (Hz)
Custom V/F curve 1st frequency point.
VFD-61 0317 N V/F V-Point 1
Variable (V)
Custom V/F curve 1st voltage point.
VFD-62 0318 N V/F F-Point 2
Variable (Hz)
Custom V/F curve 2nd frequency point.
VFD-63 0319 N V/F V-Point 2
Variable (V)
Custom V/F curve 2nd voltage point.
VFD-64 0320 N V/F F-Point 3
Variable (Hz)
Custom V/F curve 3rd frequency point.
VFD-65 0321 N V/F V-Point 3
Variable (V)
Custom V/F curve 3rd voltage point.
CODE Mod
Bus AR Display Name
Range
Description
CODE Mod
Bus AR Display Name
Range
Description
IO-00
0512 N ACI Input Sel
0_0-10V
1_0-20mA
2_4-20mA
3_PTC
4_PT100 & AFM1
5_2-10V
Selects the format of the input signal expected at the ACI input terminals
based on the type of control device to be connected—transducer, sensor,
controller, etc. This setting must correspond with ACI micro switch.
IO-01
0513 Y ACI Loss Trip
0_Disable
1_Hold Speed
2_Stop/Start
3_Trip Stop
4_At AI Loss Freq
Selects operation when ACI signal is lost.
1_VFD runs at previous speed (2 sec before signal loss)
2_VFD will restart when signal is restored
3_VFD will stay tripped until reset
4_VFD runs at frequency set in
[IO-76]
IO-02
0514 Y ACI Loss Level
0_Below Minimum
1_Below 0.5xMin
2_Redundant
Selects level for determining ACI signal loss. Redundant should be used
when two transducers Main and Spare are used for PID feedback.
NOTE:
AI Loss is disabled if min value settings is 0 V or 0 mA.
IO-03
0515 Y ACI Loss Delay
0 to 3600 sec
Duration the ACI signal is in a loss condition before initiating an ACI Loss
Trip operation.
IO-04
0516 Y ACI Filter T
0 to 20 sec
ACI time filter for noisy analog signal.
IO-05
0517 Y AVI1 Input Sel
0_0-10V
1_0-20mA
2_4-20mA
3_PTC
4_PT100 & AFM2
5_2-10V
Selects the format of the input signal expected at the ACI input terminals
based on the type of control device to be connected—transducer, sensor,
controller, etc. This setting must correspond with AVI1 micro switch.
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...