PARAMETER REFERENCE TABLES
Parameter Descriptions > VFD Menu
207
VFD-24 0280 Y DEC-4 Time
0.0 to 6000 sec
VFD will switch to ACC/DEC4 when DIs set to
XCEL-L
and
XCEL-M
are activated.
VFD-25 0281 Y S Start Time 1
0.0 to (variable) sec
ACC S-Curve Start starting Time-1
VFD-26 0282 Y S Start Time 2
0.0 to (variable) sec
ACC S-Curve Start ending Time-2
VFD-27 0283 Y S End Time 1
0.0 to (variable) sec
DEC S-Curve End starting Time-1
VFD-28 0284 Y S End Time 2
0.0 to (variable) sec
DEC S-Curve End ending Time-2
VFD-29 0285 N Skip Freq1 High
0.0 to 599 Hz
Used to bypass mechanical system resonance frequencies. If the received
speed reference is in the skip zone, VFD will run at
Low Skip Freq
until speed
reference is at or above
High Skip Freq
. Then, speed will be ramped up based
on acceleration time.
VFD-30 0286 N Skip Freq1 Low
0.0 to 599 Hz
Low frequency in skip zone 1.
VFD-31 0287 N Skip Freq2 High 0.0 to 599 Hz
High frequency in skip zone 2.
VFD-32 0288 N Skip Freq2 Low
0.0 to 599 Hz
Low frequency in skip zone 2.
VFD-33 0289 N Skip Freq3 High 0.0 to 599 Hz
High frequency in skip zone 3.
VFD-34 0290 N Skip Freq3 Low
0.0 to 599 Hz
Low frequency in skip zone 3.
VFD-35 0291 N VFD Duty Select 0_Variable Torque
1_Constant Torque
0_Variable Torque (Light Duty)
1_Constant Torque (Normal Duty)
VFD Rated Amps [VFD-47]
and
Over-Current levels [PROT-07 ~ PROT-08]
are affected
by this setting.
VFD-36 0292 Y Reset Restart
0_Disable
1_Enable
The VFD will automatically initiate operation once fault is cleared and run
command is received.
VFD-37 0293 Y DC Brake CurLvl 0.0 to 100%
Level of DC Brake Current output to the motor during start-up and stopping.
VFD-38 0294 Y DC Time at Run
0.0 to 60 sec
Duration of the DC Brake current after a run command to apply DC current
to motor to force stop motor for a stable start.
VFD-39 0295 Y DC Time at Stop 0.0 to 60 sec
Duration of the DC Brake current after a stop command to apply DC current
to the motor in order to force stop the motor.
VFD-40 0296 Y DC Stop Freq
0.0 to
[SET-23]
(Hz)
Frequency when DC Brake will begin during deceleration.
VFD-41 0297 Y Dwell T at Acc
0.0 to 600 sec
When output frequency reaches
[VFD-42]
during acceleration, VFD will hold
output at
[VFD-42]
for
[VFD-41]
timer duration. When timer expires, VFD will
continue acceleration.
VFD-42 0297 Y Dwell Hz at Acc
0.0 to
[SET-23]
(Hz)
VFD holds output frequency at
[VFD-42]
during Dwell Timer
VFD-43 0299 Y Dwell T at Dec
0.0 to 600 sec
When output frequency reaches
[VFD-44]
during deceleration, VFD will hold
output at
[VFD-44]
for
[VFD-43]
timer duration. When timer expires, VFD will
continue deceleration.
VFD-44 0300 Y Dwell Hz at Dec
0.0 to
[SET-23]
(Hz)
VFD holds output frequency at
[VFD-44]
during Dwell Timer
VFD-45 0301 Y Hopping Carrier 0_Disable
1_Enable
When enabled, VFD will automatically change carrier frequency from 2 to
5kHz (Depends on the drive frame size) in a predetermined offset pattern to
minimize audible noise from the motor.
[VFD-58]
determines a duration of
each frequency segment.
CODE Mod
Bus AR Display Name
Range
Description
Frequency
[VFD-26]
[VFD-27]
[VFD-25]
[VFD-28]
Time
60 Hz
Hz
elevados
Salto
Hz bajos
Zona de salto
de resonancia
0
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...