MAINTENANCE
Troubleshooting
175
ECnP
(74)
ExCom No power
There is no power supply on the DeviceNet
Action and Reset
Action condition
There is no power supply on the DeviceNet
Action time
Immediately
Reset method
Re-power
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• The drive detects that DeviceNet has no
power
• Check if the cable and power is normal. If yes, return to the factory for repair.
Warning Display
Description
ECo0
(84)
ExCom MTCP over
Modbus TCP exceeds maximum communication value
Action and Reset
Action condition
Hardware detection
Action time
Immediately
Reset method
Manually
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• The Master communication value is
more than the allowable quantity of the
communication card
• The upper unit is online without
communicating, and does not break off
the Modbus TCP link, causes occupy
connection
• A new Modbus TCP connection is built
every time when the upper unit is
connected to the communication card,
which caused occupy connection
• Reduce Master communication value
• Revise program of upper unit, the communication should be break off when it is not used for a long
time
• Revise program of upper unit: use the same Modbus TCP connection when connected to the same
communication card
Warning Display
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...