PARAMETER REFERENCE TABLES
Parameter Descriptions > Protection Menu
220
Parameter Descriptions > Protection Menu
AR = Adjustable while running.
ADV-53 0821 Y Main Stp Delay
1 to 65535 sec
Time delay before main pump stops when all conditions have been met.
ADV-55 0823 Y AVR Select
0_Enable AVR
1_Disable AVR
2_Disable AVR Dec
Auto Voltage Regulation Select automatically regulates the drive output
voltage to the motor rated voltage.
ADV-56 0824 N Prog-1 Setting
0_None
1_VFD Run
2_Step Freq 1
3_Step Freq 2
4_Step Freq 3
5_S-Point-A
6_S-Point-B
7_S-Point-AB
Sets Program #1 operation to Run/Stop control, Speed, or Set-point.
ADV-57 0825 N Prog-1 On Time
0 to 2400
Program #1 activation of Run/Stop control, Speed, or Set-point.
ADV-58 0826 N Prog-1 Off Time
0 to 2400
Program #1 deactivation of Run/Stop control, Speed, or Set-point.
ADV-59 0827 N Prog-1 Week Day 0000h to 007Fh
Day(s) of the week for Program #1 to operate. Binary day representation
SMTWTFS = 127 (007FH in Hexadecimal).
ADV-60 0828 N Prog-2 Setting
See
[ADV-56]
Sets Program #2operation to Run/Stop control, Speed, or Set-point.
ADV-61 0829 N Prog-2 On Time 0 to 2400
Program #2 activation of Run/Stop control, Speed, or Set-point.
ADV-62 0830 N Prog-2 Off Time 0 to 2400
Program #2 deactivation of Run/Stop control, Speed, or Set-point.
ADV-63 0831 N Prog-2 Week Day 0000h to 007Fh
Day(s) of the week for Program #2 to operate. Binary day representation
SMTWTFS = 127 (007FH in Hexadecimal).
ADV-64 0832 N Prog-3 Setting
See
[ADV-56]
Sets Program #3 operation to Run/Stop control, Speed, or Set-point.
ADV-65 0833 N Prog-3 On Time
0 to 2400
Program #3 activation of Run/Stop control, Speed, or Set-point.
ADV-66 0834 N Prog-3 Off Time 0 to 2400
Program #3 deactivation of Run/Stop control, Speed, or Set-point.
ADV-67 0835 N Prog-3 Week Day 0000h to 007Fh
Day(s) of the week for Program #3 to operate. Binary day representation
SMTWTFS = 127 (007FH in Hexadecimal).
ADV-68 0836 N Prog-4 Setting
See
[ADV-56]
Sets Program #4 operation to Run/Stop control, Speed, or Set-point.
ADV-69 0837 N Prog-4 On Time 0 to 2400
Program #4 activation of Run/Stop control, Speed, or Set-point.
ADV-70 0838 N Prog-4 Off Time 0 to 2400
Program #4 deactivation of Run/Stop control, Speed, or Set-point.
ADV-71 0839 N Prog-4 Week Day 0000h to 007Fh
Day(s) of the week for Program #4 to operate. Binary day representation
SMTWTFS = 127 (007FH in Hexadecimal).
ADV-74 0842 Y S-Point-A
0 to
[SET-20]
Activate this parameter by setting a DI (digital input)
[IO-21]
to
[IO-28]
to
48_Set-point-A
or in Scheduling program.
ADV-75 0843 Y S-Point-B
0 to
[SET-20]
Activate this parameter by setting a DI (digital input)
[IO-21]
to
[IO-28]
to
49_Set-point-B
or in Scheduling program.
ADV-76 0844 Y S-Point-AB
0 to
[SET-20]
Activate this parameter by setting a DI (digital input)
[IO-21]
to
[IO-28]
to
48_Set-point-A
and
49_Set-point-B
or in Scheduling program.
CODE Mod
Bus AR Display Name
Range
Description
CODE Mod
Bus AR Display Name
Range
Description
PROT-00 1024 N Decel Method
0_Normal
1_Over Fluxing
2_Traction Energy
0_VFD follows
Deceleration time [SET-12]
1_VFD prevents DC bus Over voltage by over-fluxing the motor at
[PROT-14]
voltage. The Decel time can be longer than
[SET-12]
value.
2_VFD prevents DC Bus Over voltage by changing output frequency and
voltage. The Decel time can be longer than
[SET-12]
value.
PROT-01 1025 Y Preheat Level
0 to 100%
Percentage of nominal current applied to the motor as DC voltage to heat
the VFD and motor. Slowly increase the percentage to reach the sufficient
preheating temperature.
PROT-02 1026 Y Preheat Duty
0 to 100%
Sets output current cycle of preheating, which corresponds to 0 to 10 sec
-
onds.
0% - no output current
50% - 5 seconds OFF and 5 seconds ON
100% - continuous output current
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...