PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
204
SET-40 0040 Y OverPress Level 0.0 to
[SET-20]
(
[SET-19]
Unit) Level the process signal (pressure) reaches to cause an overpressure condi
-
tion.
SET-41 0041 N ULD Select
0_Disabled
1_By Current
2_By Torque
Underload Detection protects against conditions such as a dry well, broken
pump, or broken drive belt. Refer to
“Underload Protection (Dry Well or Belt
.
SET-42 0042 Y ULD Level
15 to 115%
Underload Level set as a percentage of FLA (SFA). If current is below this
level and frequency is above
ULD Frequency [SET–43]
for longer than
ULD Delay
[SET–44]
timer, VFD will trip on ULD.
SET-43 0043 Y ULD Frequency
[SET-22]
to
[SET-23]
(Hz)
If motor runs above ULD Frequency, VFD compares operating current with
ULD Level [SET–42]
to detect a ULD condition.
SET-44 0044 Y ULD Delay
0 to 360 sec
Underload Delay timer before trip.
SET-45 0045 Y ULD Recovery T 0 to 720 min
Underload Recovery Time. VFD will restart from ULD trip after this time. If it
trips again, time will be doubled up to 720 min. If set to 0, fault must be
manually reset.
SET-46 0046 N ULD Recover Cnt 0 to 720 min
Decrementing counter of recovery time from an ULD trip before VFD
attempts to restart motor (Read Only).
SET-47 0047 N HLD Select
0_Disabled
1_By Current
2_By Torque
High Load Detection protects the VFD and motor against damage from an
over-torque condition. Refer to
“High Load Detection” on page 92
SET-48 0048 Y HLD Level
75 to 200%
High Load Detection level, set as a percentage of FLA (SFA). If current is
above this level and frequency is above
HLD Frequency [SET–49]
for longer than
HLD Delay [SET–50]
timer, VFD will trip on HLD.
SET-49 0049 Y HLD Frequency
[SET-22]
to
[SET-23]
(Hz)
If motor runs above HLD Frequency, VFD compares operating current with
HLD Level [SET–48]
to detect an HLD condition.
SET-50 0050 Y HLD Delay
0 to 360 sec
High Load Delay timer before trip.
SET-51
0051 Y HLD Recovery T 0 to 720 min
High Load Detection Recovery Time: VFD will restart from HLD trip after this
time. If it immediately trips again, time will be doubled up to 720 min. If set
to 0, fault must be manually reset.
SET-52 0052 Y HLD Recover Cnt 0 to 720 min
High Load Detection Recovery Count: Decrementing counter of recovery
time from a HLD trip before VFD attempts to restart motor (Read Only).
SET-53 0053 Y ACC Change Freq 0.0 to
[SET-14]
(Hz)
Frequency to switch from main accel/decel rate to second accel/decel rate.
SET-54 0054 Y Second ACC
0 to 6000 sec
Time in seconds for drive to accelerate from 0 Hz to maximum frequency.
Second acceleration occurs when frequency is above
ACC Change Freq [SET-53]
.
For example, submersibles have to be accelerated up to 30hz in 1 second
but they can accelerate from 30hz to 60hz much slower. So, we would
adjust
[SET-53]
to 30hz and the drive would follow the
[SET-11]
ACC time up to
30hz and the
[SET-54]
ACC time above 30hz.
SET-55 0055 Y Second DEC
0 to 6000 sec
When Stop Mode is set to Decelerate, time in seconds to slow down from
maximum frequency to 0 Hz. Second deceleration occurs when frequency is
above
ACC Change Freq [SET-53]
. VFD returns to main DEC time when frequency
is below
[SET-53]
-
[SET-56]
.
SET-56 0056 Y ACC/DEC Hyster 0.0 to
[SET-53]
(Hz)
When 2nd ACC/DEC time is activated and frequency drops below
[SET-53]
-
[SET-56]
, VFD will switch to main ACC/DEC time.
SET-57 0057 Y Display Line 1
0_Freq Command
1_Output Frequency
2_Multi-Fn Display
3_Output Current
Sets the parameter to display on the first line of keypad.
NOTE:
Power-cycle the drive or detach/retach keypad for display to
update.
CODE Mod
Bus AR Display Name
Range
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...