MAINTENANCE
Troubleshooting
183
PCAd
(67)
CAN/M Address
CANopen Master station address error
Action and Reset
Action condition
When the CANopen master detects an incorrect or repeated station address from the Follower, the PCAd warning dis
-
plays.
Action time
Immediately displays when the fault is detected
Reset method
Automatically
Reset condition
The warning clears when reset the station address and run the program again.
Recorded
N/A
Possible Causes
Corrective Action
• When the CANopen master detects an
incorrect or repeated station address
from the follower
• Set the correct follower station address.
Warning Display
Description
PCbF
(62)
CAN/M bus off
CANopen Master BUS off
Action and Reset
Action condition
When the CANopen master detects error packets more than 255 during the BUS off detection, or when the CANopen
card is not installed, the PCbF warning displays.
If the BUS cable is not connected, the drive will not receive issues packet, and the PCbF warning will not display.
Action time
Immediately displays when the fault is detected
Reset method
Cycle the power
Reset condition
N/A
Recorded
N/A
Possible Causes
Corrective Action
• Malfunction caused by interference
• Communication cable is broken or bad
connected
• For interference:
• Verify wiring/grounding of the communication circuit. It is recommended to separate the com
-
munication circuit from the main circuit, or wire in 90 degree for effective anti-interference
performance.
• Make sure the communication circuit is wired in series.
• Use CANopen cable or add terminating resistance.
• Check or replace the communication cable.
Warning Display
Description
PCCt
(64)
CAN/M Cycle Time
CANopen Master cycle time-out
Action and Reset
Action condition
When the transmitted packet from CANopen master exceeds the maximum allowable quantity in a certain time, the
PCCt warning displays.
Action time
Immediately displays when the fault is detected
Reset method
Automatically
Reset condition
The warning clears when changing the configuration and re-executing the program.
Recorded
N/A
Possible Causes
Corrective Action
• When the transmitted packet from
CANopen master exceeds the maximum
allowable quantity in a certain time
• Increase the time setting of D1090 synchronization cycle
Warning Display
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...