DRIVE CONFIGURATION
Default Settings Table - I/O Menu
53
Default Settings Table - I/O Menu
Parameters in highlighted rows are reset when the application is changed
[SET–00]
.
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
FE MagForce PM Motor
IO-00
ACI Input Sel
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
IO-01
ACI Loss Trip
Disable
Stop/Start Stop/Start Stop/Start Trip Stop
Trip Stop
Trip Stop
Stop/Start
Stop/Start
Trip Stop
IO-02
ACI Loss Level
Below
Minimum
Below
Minimum
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
IO-03
ACI Loss Delay
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
IO-04
ACI Filter T
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
IO-05
AVI1 Input Sel
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
IO-06
AVI1 Loss Trip
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-07
AVI1 Loss Lvl
Below
Minimum
Below
Minimum
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
Below
Minimum
Below
Minimum
Below
0.5xMin
Below
0.5xMin
IO-08
AVI1 Loss Delay
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
IO-09
AVI1 Filter T
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
IO-10
AVI2 Filter T
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
IO-11
Spare Max Value
1 inWC
1 inWC
1 inWC
150 °F
200 PSI
200 PSI
200 inWC
200 PSI
200 PSI
200 inWC
IO-12
Spare AI Select
AVI1
AVI1
AVI1
AVI1
AVI1
AVI1
AVI1
AVI1
AVI1
AVI1
IO-13
F/B PT Status
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only
Read Only
Read Only
IO-14
PID Filter Time
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
IO-15
PID Delay Time
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
IO-16
Limit by Level
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-17
Max Limit Level
6 Feet
0.9 inWC
0.9 inWC
140 °F
50 PSI
6 Feet
50 PSI
50 PSI
6 Feet
6 Feet
IO-18
Min Limit Level
3 Feet
0.8 inWC
0.8 inWC
130 °F
40 PSI
3 Feet
40 PSI
40 PSI
3 Feet
3 Feet
IO-19
Min Freq Limit
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
40 Hz
80 Hz
80 Hz
IO-20
DI Filter
0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec
0.005 Sec
0.005 Sec 0.005 Sec
0.005 Sec
0.005 Sec
IO-21
MI1 Define
Speed-L
None
None
None
None
None
None
None
None
None
IO-22
MI2 Define
Speed-M
None
None
None
None
None
None
None
None
None
IO-23
MI3 Define
Speed-H
None
None
None
None
None
None
None
None
None
IO-24
MI4 Define
Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset
IO-25
MI5 Define
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
IO-26
MI6 Define
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
IO-27
MI7 Define
None
None
None
None
None
None
None
None
None
None
IO-28
MI8 Define
None
None
None
None
None
None
None
None
None
None
IO-29
FO Enable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-30
FO Frequency
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
115 Hz
115 Hz
IO-31
FO Fault Retry
10
10
10
10
10
10
10
10
10
10
IO-32
FO Retry Delay
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
IO-33
FO Mode & Reset
PID Off
Auto
PID On
Auto
PID On
Auto
PID On
Auto
PID On
Auto
PID On Auto
PID On
Auto
PID Off
Auto
PID On Auto
PID Off
Auto
IO-34
FO PID S-Point
0 inWC
0 inWC
0 inWC
0 °F
0 PSI
0 PSI
0 inWC
0 PSI
0 PSI
0 inWC
IO-35
Ext Trip Mode
Coast
Coast
Coast
Coast
Coast
Coast
Coast
Coast
Coast
Coast
IO-36
Damper Mode
Disable
Enable
Enable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-37
Damper T-Delay
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
IO-38
No-Flow Mode
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-39
Prime Time
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
IO-40
No-Flow Freq
20 Hz
20 Hz
20 Hz
20 Hz
20 Hz
30 Hz
20 Hz
20 Hz
60 Hz
40 Hz
IO-41
Lube/S-Clean
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-42
S-Clean Timer
60 Min
60 Min
60 Min
60 Min
60 Min
60 Min
60 Min
60 Min
60 Min
60 Min
IO-43
Pre-Lube Timer
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
IO-44
Run-Lube Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
IO-45
Post-Lube Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
IO-46
DI NO/NC
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...