PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
205
SET-58 0058 Y Display Line 3
0_Output Current (A)
1_Counter value (c)
2_Output Freq (H)
3_DC-Bus Voltage (u)
4_Output Voltage (E)
5_Output Power (P)
6_Motor Speed (r)
7_PID Feedback % (b)
8_AVI1 Value (1)
9_ACI Value (2)
10_AVI2 Value (3)
11_IGBT Temp °C (i)
12_CAP Temp °C (c)
13_D-Inputs Status (i)
14_D-Out Status (o)
15_Ground Flt Lvl (G)
16_DC Bus Ripple (r)
17_PLC Data D1043 (C)
18_Fan Speed (F)
19_VFD Status (6)
20_kWh Display (J)
21_PID Set-point (L)
22_Aux Analog Input
23_Commu Role
24_This VFD Status
25_Pump Role
26_Network Status
27_Session Status
28_Active VFD Num
29_Active Lag Num
30_Active Stdby Num
Sets the parameter to display on third line of keypad. The new selection will
be shown when VFD power is cycled or keypad is disconnected and recon
-
nected again.
SET-59 0059 Y Keypad Freq
0.0 to
[VFD-00]
(Hz)
The keypad frequency setting.
SET-60 0060 Y HOA Mode
Source
0_Keypad
1_Digital Input
2_RS485 Serial
3_Com Card
Sets the input that selects between Hand-Off-Auto modes
SET-61 0061 N KPD STOP as OFF 0_Disable
1_Enable
When enabled, the
STOP
key acts as an OFF position on keypad HOA and will
stop the VFD in all Hand and Auto Run CMD modes except an External HOA.
When VFD is stopped by
STOP
key, to return to Auto or Hand mode press the
HAND
or
AUTO
key.
SET-62 0062 N Carrier Freq
2.0 to 15.0 kHz
Varies by VFD rating
VFD switching frequency. Higher frequencies create more precise wave
forms, but generate higher heat. Lower frequencies run cooler, but could
potentially cause audible noise, which can be eliminated by adjusting this
carrier frequency during stop.
SET-63 0063 N 2/3-Wire Select 0_2-Wire Fwd/Rev
1_2-Wire Fwd+Rev
2_3-Wire F+R+Stop
0_ FWD input provides forward run command and REV input provides a
reverse run command. VFD ignores the command if both inputs are acti
-
vated.
1_ FWD input provides forward run command and REV input changes the
rotation.
2_ FWD input provides forward run command, REV input changes the rota
-
tion, and Stop stops the drive
CODE Mod
Bus AR Display Name
Range
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...