MAINTENANCE
Troubleshooting
176
ECo1
(85)
ExCom EIP over
Ethernet/IP exceeds maximum communication value
Action and Reset
Action condition
Hardware detection
Action time
Immediately
Reset method
Manually
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• The Master communication value is
more than the allowable quantity of the
communication card
• The upper unit is online without
communicating, and does not break off
the Modbus TCP link, causes occupy
connection
• A new Modbus TCP connection is built
every time when the upper unit is
connected to the communication card,
which caused occupy connection
• Reduce Master communication value
• Revise program of upper unit, the communication should be break off when it is not used for a long
time
• Revise program of upper unit: use the same Modbus TCP connection when connected to the same
communication card
Warning Display
Description
ECPi
(79)
ExCom Conf data
Profibus configuration data error
Action and Reset
Action condition
N/A
Action time
N/A
Reset method
Manually
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• The GSD file is incorrect
• Get the correct GSD file from the software.
Warning Display
Description
ECPP
(78)
ExCom Pr data
Profibus parameter data error
Action and Reset
Action condition
N/A
Action time
N/A
Reset method
Manually
Reset condition
Immediately
Recorded
N/A
Possible Causes
Corrective Action
• The GSD file is incorrect
• Get the correct GSD file from the software
Warning Display
Description
Содержание CERUS X-DRIVE CXD-003A-4V
Страница 1: ...franklin electric com ENGLISH EN CERUSX DRIVE Installation and Operation Manual Firmware Version 1 2 ...
Страница 2: ......
Страница 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Страница 96: ...OPERATION Protection Features 96 ...
Страница 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Страница 124: ...COMMUNICATIONS BACnet Communication 124 ...
Страница 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Страница 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Страница 132: ...ACCESSORIES Optional Extension Cards 132 ...
Страница 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Страница 250: ...GLOSSARY 250 ...
Страница 252: ...For technical assistance parts or repair please contact 800 348 2420 franklin electric com 10000005064 Rev 004 09 22 ...