1.0 INTRODUCTION
UL S2203
CyberCat 50 Operation Manual
1-29
FM 3029134
P/N: 06-368-2
Rev 4, 08/2013
Exhibit 1-27: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Voice EVAC
Amplifier
Common
Application Type
Y
Single Channel
/ Dual
Channel / Page Only
1
Miscellaneous
Peripheral Address
Y
2
- 32
Locality Y
Standard
/ Boston / Chicago
/ NYC
Standard 2
Record and Repeat Tones
Y
Play Tones
/ No Tones
Play
Tones
3
Speaker Voltage Output
Y
25 VAC /
70.7 VAC
Power Input
Y
120 VAC
/ 240 VAC
Audio Bus
Y
Enabled
/ Disabled
Local Microphone
Y
Enabled /
Disabled
Battery Charger
Y
Enabled
/ Disabled
Local Piezo
Y
Enabled
/ Disabled
NAC
State Y
Alarm
/ Pre Alarm 2 / Pre
Alarm 1 / Supervisory /
Trouble / Process
Synchronization Y
None
/ Gentex / System
Sensor
Zones
Y
1 – 254
4
Silenceable Y
Silence
/ Non-Silence
Drill Y
Enabled
/ Disabled
Walk Test
Y
Enabled / Disabled
Active During Fire Playback
Y
Enabled /
Disabled
5
Active During Fire Page
Y
Enabled /
Disabled
5
Active During MNS Playback
Y
Enabled /
Disabled
5
Active During MNS Page
Y
Enabled /
Disabled
5
NAC Delay Timeout
Y
0
– 250 seconds
Contact Monitor
Contact Y
Disabled
/ Enabled
Message 1
Y
Select ID number (1 – 16)
Message 2
Y
Select ID number (1 – 16)
Notes:
1.
Select the type of application that the amplifier is being utilized as.
2.
Locality setting is configured for operation of local jurisdiction requirements for only Boston, Chicago and New York. Outside of
these jurisdiction then the setting should be set to Standard
3.
Allows the selection to play MNS tone and Fire tones between record and repeat messages.
4.
Select the zone number(s) that will activate the NAC.
5.
These need to be enabled when you want the NAC circuit on the Amplifier to activate off of an event.