1.0 INTRODUCTION
1-18
CyberCat 50 Operation Manual
UL S2203
Rev 4, 08/2013
P/N: 06-368-2
FM 3029134
Exhibit 1-16: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Releasing
Module)
Common
Loop Number of Device
Y
1
1
Address of Device
Y
1
– 50
Output Y
Enabled
/Disabled
Custom Message
Y
60 character user defined
(1-001 RELEASING MOD
Loop 1 - Address 001)
Y
Default/
User Defined
Zone Assignments
Y
1
– 253
(3 zones available)
Output Type
Y
No Output
/ Solenoid /
Expanded Solenoid /
Masterbox
Output State
Y
No Output State
/ Alarm
Defaults
(FAAST
Detector)
Common
Loop Number of Device
Y
1
1
Address of Device
Y
1 – 254
Custom Message
Y
60 character user defined
(1-001 FAAST DETECT
Loop 1 - Address 001)
Y
Default/
User Defined
Zone Assignments
Y
1
– 253
2
Walktest Y
Enabled /
Disabled
Y
0.1% - 0.99645% ft. (slider)
States
State Assignments
Fire 2 / Fire 1 / Action 2 / Action
1 / Alert
Y
Disabled
/ Alarm / PreAlarm
2 / PreAlarm 1 / Supervisory /
Process
3
Y
Latching /
Non-Latching
4
Alarm Verification Timers
Fire 2 / Fire 1 / Action 2 / Action
1 / Alert
Y
No Timer
/ Timer 1 / Timer 2
/ Timer 3
5
Verification Timer Values
Timer 1 / Timer 2 / Timer 3
Y
0
– 255 (seconds)
Acclimate
Acclimate Y
Disabled
/ Enabled
Acclimate High Range
Y
Range 1-H
(0.00046%ft – 0.04980%ft)
Range 2-M
(0.05%ft – 0.09982%ft)
Range 3-M
(0.1%ft – 0.99645%ft)
Range 4-L
(1%ft – 3.98818%ft)
6
Notes:
1.
CyberCat 50 has only one (1) addressable loop with a maximum of 50 devices.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
Each detection level on the FAAST detector can be mapped to a panel state (user defined).
4.
Each detection level can be configured as a latching or non-latching event.
Must be latching if configured for alarm
.
5.
Each detection level can be configured to initiate one of three Alarm Verification timers.
6.
Allows you to set the high sensitivity level for the selected acclimate range.